Configuring the Dual-Meter Connection
Configuring Dual-Meter Connection Using SetApp
In the sample configuration described below, a SolarEdge energy meter with Modbus
connection is configured as a production meter, and is set to address 1, while an inline
meter is configured as an export/import meter, and is set to address 2.
To configure the SolarEdge energy meter with Modbus connection using SetApp:
1. Verify that the meter at address 1 is configured as a production meter. From the
SetApp main menu, select
Communication
è
RS485-x
è
Meter 1
2. Verify the value of the following parameters:
Meter Function
è
Inverter Production
Protocol
è
SolarEdge
Device ID
è
1
3. Select
Meter 2
to configure the export/import meter in the following steps:
4. Select
Meter Function
, and select
Import
.
5. Set the inline meter's Modbus ID to address 2.
Verifying Meter Connections
Verifying the Meter Connections using SetApp
To verify the connectivity of two meters using SetApp, refer to
Meter Connection using SetApp on page 33
Troubleshooting Dual-Meter Connections
Troubleshooting Dual-Meter Connections using SetApp
To troubleshoot the connectivity of two meters using SetApp, refer to
the Meter using SetApp on page 36