Connecting Inverters/chargers/UPS to the battery unit while is ON can cause big sparks due to
capacitors inside the connected device. This can be harmful for people.
Connecting main battery terminal must be with correct size cable.
based on the rated current of the battery and the charger/inverter in case it is lower.
Step 2
. Connect the negative cable to the battery negative busbar and positive cable to the
8
Figure
5
connection terminals
SS4074-11 INSTALLATION MANUAL v1.0
battery positive busbar as shown in figure 5.