Unit 23, Alternator Park
Montague Gardens 7441
Cape Town, South Africa
Solar MD (PTY) ltd.
T: (021) 555 2181
.
Switching the Battery ON
Step 1
. Make sure all DC cables are tightened according specifications.
Step 2
. If the battery operates in parallel with other Energy sources, make sure that the
difference between battery voltage and DC bus is not more than 2.5V. If greater than 2.5V
please Charge or Discharge the other source accordingly until voltage difference is in safe
ranges under 2.5V.
A hot connection with difference in voltage can cause very high
equalization current which can burn the fuses of the battery!
Measure the voltage of the battery before connecting the dc
Cables.
Step 5
. Hold multi purpose button until the light comes on.
If the battery does not switch the main protection Contact ON in 7
sec, please check BMS board indication LED for faults. See section BMS Error
and Warnings.
9
SS4074-11 INSTALLATION MANUAL v1.0
Step 3. Turn the BMS board ON/OFF switch to the ON position (figure 4 pos 3).
Step 4. Connect Multipurpose button if not connected to the BMS board connector (figure 4
pos 5).