TROUBLE SHOOTING
Heater does not come on, t in display
….The heater pre-set trip temperature IS ABOVE THE AMBIENT
TEMPERATURE. This can be adjusted using the temperature set point potentiometer.
Heater does not come on, flashing DOT
…The controller is waiting for input from optional occupancy sensor
or pushbutton. If your system does not utilize the occupancy sensor or a pushbutton, then wire jumper (factory
installed) must be in place in PIR SENSOR INPUT on pins SIG IN and COM. If the jumper is not in place,
controller will not operate.
SPECIFICATIONS
Max load at 20°C ambient
Voltage
Power Consumption
Occupancy Sensor (option)
Pushbutton Timer (option)
Set Time Period
Temperature Set point
Factory Set Temperature trip point
2 heater Installation
Ambient Operating Temperature
IP Rating
Max Unit Operating Temperature
Occupancy Sensor
(optional)
Operating Voltage
Direction
Detection
8.0kW @ 208-240VAC or
4.0kW @ 120VAC
120Vac or 208-/- 10%50/60Hz
50mA
See below
Momentary or Toggle
1-60 minutes
5°C to 25°C
25°C
Must be fitted in Parallel
-20°C to 30°C
IP65
65°C
12V dc
90° Adjustable
45’ (18 Meters)
WARNING: Solaira SMaRT 34-DV Variable control is a high power
electrical device and MUST ONLY BE INSTALLED BY A CERTIFIED
ELECTRICIAN TO LOCAL AND NATIONAL ELECTRICAL CODE