Solair J A Series Installation Instructions Manual Download Page 4

Manual 2100-553
Page

4 of 28

WALL MOUNT GENERAL INFORMATION

AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE

J

42

A

1

A

10

X

X

X

X

X

J

NOTE:  Vent option X is without exhaust capability.  May require separate field supplied barometric relief in building.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be
checked for external signs of shipping damage.  If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation.  Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 3 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

KW

MODEL NUMBER

CONTROL MODULES

 See Spec. Sheets:

 S3438, S3439 &/or S3440

VOLTS & PHASE

A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3

REVISIONS

VENTILATION OPTIONS

X - Barometric Fresh Air Damper (Standard)
See Vent & Control Options Table 14.

FILTER OPTIONS

P - Two Inch Pleated

COLOR OPTIONS

X - Beige

COIL OPTIONS

X - Standard

OUTLET OPTIONS

X - Front (Standard)

CAPACITY

17 - 1½ Ton
24 - 2 Ton
30 - 2½ Ton
36 - 3 Ton
42 - 3½ Ton
48 - 4 Ton
60 - 5 Ton
70 - 6 Ton

A - Right Hand Air Conditioner
L - Left Hand Air Conditioner

Summary of Contents for J A Series

Page 1: ...TIONS WALL MOUNTED PACKAGE AIR CONDITIONERS LOW VOLTAGE CONTROL CIRCUIT WIRING MODELS J17A1 J17L1 J24A1 J24L1 J30A1 J30L1 J36A1 J36L1 J42A1 J42L1 J48A1 J48L1 J60A1 J60L1 J70A1 J70L1 Manual 2100 553 Su...

Page 2: ...Heat No Econ 15 Figure 9 A C with EIFM Economizer 16 Figure 10 A C w ECONWMT Econ 17 Figure 11 Fan Blade Setting 21 Start Up General 18 Topping Off System Charge 18 Safety Practices 18 Important Insta...

Page 3: ...Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Ham...

Page 4: ...e particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or lo...

Page 5: ...G2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient s...

Page 6: ...roughly inspected to insure that they are capable of carrying the weight of the installed unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outsid...

Page 7: ...Back View L M O E R S S S S S T 44 N Q P B 1 Dimension is 21 00 inches on J70A J70L models 2 Optional top outlet factory installed only for J30A and J36A models only FIGURE 2 l a n i m o N s t n e m e...

Page 8: ...ENING ENTIRE LENGTH OF TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE NOTES RAIN FLASHING HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILI...

Page 9: ...4 CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF...

Page 10: ...B C D E 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 RETURN AIR FOAM AIR SEAL OPENING 29 Wall Opening and Hole Location View NOTES Supply Opening SUPPLY AIR Return Opening IT IS RECOMMENDED THAT A B...

Page 11: ...y air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could r...

Page 12: ...000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A...

Page 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 14: ...up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on three phase scroll compressor start ups S...

Page 15: ...N GROUNDED FAN BLOWER 24V HOT OPEN OR SPECIAL USE AS REQUIRED COMPRESSOR ELECTRIC HEAT STAGE 2 N C CONTACT N O CONTACT COMMON VENTILATION IF EQUIPPED OPEN OR SPECIAL USE AS REQUIRED J MODULE REFRIGERA...

Page 16: ...TS WITH 15 OR MORE KW FACTORY INSTALLED JUMPER REMOVE FOR 2 STAGE OPERATION OPEN OR SPECIAL USE AS REQUIRED PURPLE BLUE 24V COMMON GROUNDED FAN BLOWER 24V HOT COMPRESSOR ELECTRIC HEAT STAGE 2 ECONOMIZ...

Page 17: ...STAGE 1 ECONOMIZER STAGE 1 OPEN OR SPECIAL USE AS REQUIRED RED PURPLE YELLOW RED BLUE 24V COMMON GROUNDED FAN BLOWER ELECTRIC HEAT STAGE 2 24V HOT 1 1 J MODULE REFRIGERANT IF EQUIPPED BROWN WHITE FACT...

Page 18: ...aks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used af...

Page 19: ...n reverse rotation for several minutes the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing is determined for...

Page 20: ...ockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch the cont...

Page 21: ...8 1 5 1 9 1 6 1 The correct system R 410A charge is shown on the unit nameplate Optimum unit performance will occur with a refrigerant charge resulting in a liquid subcooling as shown in Table 5 If ch...

Page 22: ...1 3 1 5 4 4 3 3 1 0 7 4 6 3 1 6 9 4 8 3 1 4 2 5 0 4 1 2 5 5 3 4 1 1 8 5 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 2 3 1 9 5 3 4 3 1 2 8 3 6 3 1 6 0 4 8 3 1 1 3 4 0 4 1 6 5 4 2 4 1 2 8...

Page 23: ...0 1 0 1 0 1 Z 0 C 0 0 C 1 A 0 3 J 6 0 C 9 0 C 5 1 C 3 0 6 4 1 1 1 1 1 1 2 1 7 1 6 2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A 0 0 A 1 A 6 3 J 5 0 A 8 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 1...

Page 24: ...8 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 1 2 r o 1 4 2 2 3 8 4 8 5 4 8 5 3 5 3 0 5 0 6 0 9 8 8 8 6 4 0 1 0 1 0 1 0 1 8 8 5 6 2 0 6 0 3 6 0 1 0 1 0 1 Z 0 B 0 0 B 1 L 0 3 J 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1...

Page 25: ...l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 3 4 5 0 2 0 1 0 6 9 5 6 8 0 2 8 5 3 7 5 1 6 5 7 9 5 0 9 0 0 8 5 3 7 0 5 6 5 3 5 5 9 3 1 0 4 3 1 5 8 2 1 5 0 2 1 0 1...

Page 26: ...1 0 5 6 3 1 4 4 1 0 4 2 0 1 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 2 7 0 0 5 0 2 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 0 1 6...

Page 27: ...0 B A 6 3 W H E X 9 0 B 3 0 A W H E X X 5 1 B 7 3 A W H E X X 6 0 C A 3 0 C W H E X X 9 0 C A 3 0 C W H E X X 5 1 C A 3 0 A W H E X X 5 0 A 5 0 A W H E X X 0 1 A 5 0 A W H E X X X X 5 1 A 5 0 A W H E...

Page 28: ...D 2 D A F B d r a d n a t S r e p m a D r i A h s e r F c i r t e m o r a B X B 2 M F I E r e z i m o n o c E X 3 D A F B d r a d n a t S r e p m a D r i A h s e r F c i r t e m o r a B X C 3 M F I E...

Reviews: