Solair J A Series Installation Instructions Manual Download Page 18

Manual 2100-553
Page

18 of 28

START UP

THESE UNITS REQUIRE R-410A
REFRIGERANT AND POLYOL
ESTER OIL.

GENERAL:

1. Use separate service equipment to avoid cross

contamination of oil and refrigerants.

2. Use recovery equipment rated for R-410A

refrigerant.

3. Use manifold gauges rated for R-410A (800 psi/250

psi low).

4. R-410A is a binary blend of HFC-32 and HFC-125.

5. R-410A is nearly azeotropic - similar to R-22 and

R-12.  Although nearly azeotropic, charge with
liquid refrigerant.

6. R-410A operates at 40-70% higher pressure than

R-22, and systems designed for R-22 cannot
withstand this higher pressure.

7. R-410A has an ozone depletion potential of zero,

but must be reclaimed due to its global warming
potential.

8. R-410A compressors use polyolester oil.

9. Polyol Ester oil is hygroscopic; it will rapidly absorb

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used - even a deep

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug

compressor immediately after removal.  Purge with
small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Solair recommends
reclaiming, evacuating (see criteria above), and charging
to the nameplate charge.  If done correctly, topping off
the system charge can be done without problems.

With R-410A, there are no significant changes in the
refrigerant composition during multiple leaks and
recharges.  R-410A refrigerant is close to being an
azeotropic blend (it behaves like a pure compound or
single component refrigerant).  The remaining
refrigerant charge, in the system, may be used after
leaks have occurred and then “top-off” the charge by
utilizing the charging charts on the inner control panel
cover as a guideline.

REMEMBER:  

When adding R-410A refrigerant, it

must come out of the charging cylinder/tank as a liquid
to avoid any fractionation, and to insure optimal system
performance.  Refer to instructions for the cylinder that
is being utilized for proper method of liquid extraction.

SAFETY PRACTICES:

1. Never mix R-410A with other refrigerants.

2. Use gloves and safety glasses, Polyol Ester oils can

be irritating to the skin, and liquid refrigerant will
freeze the skin.

3. Never use air and R-410A to leak check; the

mixture may become flammable.

4. Do not inhale R-410A – the vapor attacks the

nervous system, creating dizziness, loss of
coordination and slurred speech.  Cardiac
irregularities, unconsciousness and ultimate death
can result from breathing this concentration.

5. Do not burn R-410A.  This decomposition

produces hazardous vapors.  Evacuate the area if
exposed.

6. Use only cylinders rated DOT4BA/4BW 400.

7. Never fill cylinders over 80% of total capacity.

8. Store cylinders in a cool area, out of direct

sunlight.

9. Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge

lines or cylinders.  R-410A expands significantly
at warmer temperatures.  Once a cylinder or line is
full of liquid, any further rise in temperature will
cause it to burst.

        WARNING

Failure to conform to these practices
could lead to damage, injury or death.

Summary of Contents for J A Series

Page 1: ...TIONS WALL MOUNTED PACKAGE AIR CONDITIONERS LOW VOLTAGE CONTROL CIRCUIT WIRING MODELS J17A1 J17L1 J24A1 J24L1 J30A1 J30L1 J36A1 J36L1 J42A1 J42L1 J48A1 J48L1 J60A1 J60L1 J70A1 J70L1 Manual 2100 553 Su...

Page 2: ...Heat No Econ 15 Figure 9 A C with EIFM Economizer 16 Figure 10 A C w ECONWMT Econ 17 Figure 11 Fan Blade Setting 21 Start Up General 18 Topping Off System Charge 18 Safety Practices 18 Important Insta...

Page 3: ...Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Ham...

Page 4: ...e particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or lo...

Page 5: ...G2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient s...

Page 6: ...roughly inspected to insure that they are capable of carrying the weight of the installed unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outsid...

Page 7: ...Back View L M O E R S S S S S T 44 N Q P B 1 Dimension is 21 00 inches on J70A J70L models 2 Optional top outlet factory installed only for J30A and J36A models only FIGURE 2 l a n i m o N s t n e m e...

Page 8: ...ENING ENTIRE LENGTH OF TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE NOTES RAIN FLASHING HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILI...

Page 9: ...4 CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF...

Page 10: ...B C D E 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 RETURN AIR FOAM AIR SEAL OPENING 29 Wall Opening and Hole Location View NOTES Supply Opening SUPPLY AIR Return Opening IT IS RECOMMENDED THAT A B...

Page 11: ...y air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could r...

Page 12: ...000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A...

Page 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 14: ...up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on three phase scroll compressor start ups S...

Page 15: ...N GROUNDED FAN BLOWER 24V HOT OPEN OR SPECIAL USE AS REQUIRED COMPRESSOR ELECTRIC HEAT STAGE 2 N C CONTACT N O CONTACT COMMON VENTILATION IF EQUIPPED OPEN OR SPECIAL USE AS REQUIRED J MODULE REFRIGERA...

Page 16: ...TS WITH 15 OR MORE KW FACTORY INSTALLED JUMPER REMOVE FOR 2 STAGE OPERATION OPEN OR SPECIAL USE AS REQUIRED PURPLE BLUE 24V COMMON GROUNDED FAN BLOWER 24V HOT COMPRESSOR ELECTRIC HEAT STAGE 2 ECONOMIZ...

Page 17: ...STAGE 1 ECONOMIZER STAGE 1 OPEN OR SPECIAL USE AS REQUIRED RED PURPLE YELLOW RED BLUE 24V COMMON GROUNDED FAN BLOWER ELECTRIC HEAT STAGE 2 24V HOT 1 1 J MODULE REFRIGERANT IF EQUIPPED BROWN WHITE FACT...

Page 18: ...aks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used af...

Page 19: ...n reverse rotation for several minutes the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing is determined for...

Page 20: ...ockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch the cont...

Page 21: ...8 1 5 1 9 1 6 1 The correct system R 410A charge is shown on the unit nameplate Optimum unit performance will occur with a refrigerant charge resulting in a liquid subcooling as shown in Table 5 If ch...

Page 22: ...1 3 1 5 4 4 3 3 1 0 7 4 6 3 1 6 9 4 8 3 1 4 2 5 0 4 1 2 5 5 3 4 1 1 8 5 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 2 3 1 9 5 3 4 3 1 2 8 3 6 3 1 6 0 4 8 3 1 1 3 4 0 4 1 6 5 4 2 4 1 2 8...

Page 23: ...0 1 0 1 0 1 Z 0 C 0 0 C 1 A 0 3 J 6 0 C 9 0 C 5 1 C 3 0 6 4 1 1 1 1 1 1 2 1 7 1 6 2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A 0 0 A 1 A 6 3 J 5 0 A 8 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 1...

Page 24: ...8 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 1 2 r o 1 4 2 2 3 8 4 8 5 4 8 5 3 5 3 0 5 0 6 0 9 8 8 8 6 4 0 1 0 1 0 1 0 1 8 8 5 6 2 0 6 0 3 6 0 1 0 1 0 1 Z 0 B 0 0 B 1 L 0 3 J 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1...

Page 25: ...l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 3 4 5 0 2 0 1 0 6 9 5 6 8 0 2 8 5 3 7 5 1 6 5 7 9 5 0 9 0 0 8 5 3 7 0 5 6 5 3 5 5 9 3 1 0 4 3 1 5 8 2 1 5 0 2 1 0 1...

Page 26: ...1 0 5 6 3 1 4 4 1 0 4 2 0 1 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 2 7 0 0 5 0 2 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 0 1 6...

Page 27: ...0 B A 6 3 W H E X 9 0 B 3 0 A W H E X X 5 1 B 7 3 A W H E X X 6 0 C A 3 0 C W H E X X 9 0 C A 3 0 C W H E X X 5 1 C A 3 0 A W H E X X 5 0 A 5 0 A W H E X X 0 1 A 5 0 A W H E X X X X 5 1 A 5 0 A W H E...

Page 28: ...D 2 D A F B d r a d n a t S r e p m a D r i A h s e r F c i r t e m o r a B X B 2 M F I E r e z i m o n o c E X 3 D A F B d r a d n a t S r e p m a D r i A h s e r F c i r t e m o r a B X C 3 M F I E...

Reviews: