Solair J A Series Installation Instructions Manual Download Page 19

Manual

2100-553

Page

19 of 28

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil
with a dish washing detergent.

HIGH PRESSURE SWITCH

All J**A/J**L wall mounted air conditioner series
models are supplied with a remote reset for the high and
low pressure switch.  If tripped, this pressure switch may
be reset by turning the thermostat off then back on again.

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as substantially
reduced current draw compared to tabulated values.

Verification of 

proper rotation

 must be made at the

time the equipment is put into service.  If improper
rotation is corrected at this time, there will be no
negative impact on the durability of the compressor.
However, reverse operation for over one hour may have
a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse rotation

for several minutes, the compressor’s internal
protector will trip.

All three phase compressors are wired identically
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

PHASE MONITOR

All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  

Do not reverse any of the unit factory

wires as damage may occur.

CONDENSER FAN OPERATION

Applies to J42, J48, J60 and J70 models only.

  The

condenser fan motor on 230/208 volt, one and three
phase, 60 HZ units is a two-speed motor that comes
factory wired on high speed for peak performance.  If
ambient conditions permit, it can be reconnected to low
speed (red wire) for lower sound level.  See wiring
diagram.

SERVICE HINTS

1. Caution owner/operator to maintain clean air filters

at all times.  Also, not to needlessly close off supply
and return air registers.  This reduces airflow
through the system, which shortens equipment
service life as well as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

START UP (Continued)

Summary of Contents for J A Series

Page 1: ...TIONS WALL MOUNTED PACKAGE AIR CONDITIONERS LOW VOLTAGE CONTROL CIRCUIT WIRING MODELS J17A1 J17L1 J24A1 J24L1 J30A1 J30L1 J36A1 J36L1 J42A1 J42L1 J48A1 J48L1 J60A1 J60L1 J70A1 J70L1 Manual 2100 553 Su...

Page 2: ...Heat No Econ 15 Figure 9 A C with EIFM Economizer 16 Figure 10 A C w ECONWMT Econ 17 Figure 11 Fan Blade Setting 21 Start Up General 18 Topping Off System Charge 18 Safety Practices 18 Important Insta...

Page 3: ...Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Ham...

Page 4: ...e particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or lo...

Page 5: ...G2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient s...

Page 6: ...roughly inspected to insure that they are capable of carrying the weight of the installed unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outsid...

Page 7: ...Back View L M O E R S S S S S T 44 N Q P B 1 Dimension is 21 00 inches on J70A J70L models 2 Optional top outlet factory installed only for J30A and J36A models only FIGURE 2 l a n i m o N s t n e m e...

Page 8: ...ENING ENTIRE LENGTH OF TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE NOTES RAIN FLASHING HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILI...

Page 9: ...4 CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF...

Page 10: ...B C D E 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 RETURN AIR FOAM AIR SEAL OPENING 29 Wall Opening and Hole Location View NOTES Supply Opening SUPPLY AIR Return Opening IT IS RECOMMENDED THAT A B...

Page 11: ...y air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could r...

Page 12: ...000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A...

Page 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 14: ...up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on three phase scroll compressor start ups S...

Page 15: ...N GROUNDED FAN BLOWER 24V HOT OPEN OR SPECIAL USE AS REQUIRED COMPRESSOR ELECTRIC HEAT STAGE 2 N C CONTACT N O CONTACT COMMON VENTILATION IF EQUIPPED OPEN OR SPECIAL USE AS REQUIRED J MODULE REFRIGERA...

Page 16: ...TS WITH 15 OR MORE KW FACTORY INSTALLED JUMPER REMOVE FOR 2 STAGE OPERATION OPEN OR SPECIAL USE AS REQUIRED PURPLE BLUE 24V COMMON GROUNDED FAN BLOWER 24V HOT COMPRESSOR ELECTRIC HEAT STAGE 2 ECONOMIZ...

Page 17: ...STAGE 1 ECONOMIZER STAGE 1 OPEN OR SPECIAL USE AS REQUIRED RED PURPLE YELLOW RED BLUE 24V COMMON GROUNDED FAN BLOWER ELECTRIC HEAT STAGE 2 24V HOT 1 1 J MODULE REFRIGERANT IF EQUIPPED BROWN WHITE FACT...

Page 18: ...aks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used af...

Page 19: ...n reverse rotation for several minutes the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing is determined for...

Page 20: ...ockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch the cont...

Page 21: ...8 1 5 1 9 1 6 1 The correct system R 410A charge is shown on the unit nameplate Optimum unit performance will occur with a refrigerant charge resulting in a liquid subcooling as shown in Table 5 If ch...

Page 22: ...1 3 1 5 4 4 3 3 1 0 7 4 6 3 1 6 9 4 8 3 1 4 2 5 0 4 1 2 5 5 3 4 1 1 8 5 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 2 3 1 9 5 3 4 3 1 2 8 3 6 3 1 6 0 4 8 3 1 1 3 4 0 4 1 6 5 4 2 4 1 2 8...

Page 23: ...0 1 0 1 0 1 Z 0 C 0 0 C 1 A 0 3 J 6 0 C 9 0 C 5 1 C 3 0 6 4 1 1 1 1 1 1 2 1 7 1 6 2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A 0 0 A 1 A 6 3 J 5 0 A 8 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 1...

Page 24: ...8 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 1 2 r o 1 4 2 2 3 8 4 8 5 4 8 5 3 5 3 0 5 0 6 0 9 8 8 8 6 4 0 1 0 1 0 1 0 1 8 8 5 6 2 0 6 0 3 6 0 1 0 1 0 1 Z 0 B 0 0 B 1 L 0 3 J 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1...

Page 25: ...l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 3 4 5 0 2 0 1 0 6 9 5 6 8 0 2 8 5 3 7 5 1 6 5 7 9 5 0 9 0 0 8 5 3 7 0 5 6 5 3 5 5 9 3 1 0 4 3 1 5 8 2 1 5 0 2 1 0 1...

Page 26: ...1 0 5 6 3 1 4 4 1 0 4 2 0 1 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 2 7 0 0 5 0 2 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 0 1 6...

Page 27: ...0 B A 6 3 W H E X 9 0 B 3 0 A W H E X X 5 1 B 7 3 A W H E X X 6 0 C A 3 0 C W H E X X 9 0 C A 3 0 C W H E X X 5 1 C A 3 0 A W H E X X 5 0 A 5 0 A W H E X X 0 1 A 5 0 A W H E X X X X 5 1 A 5 0 A W H E...

Page 28: ...D 2 D A F B d r a d n a t S r e p m a D r i A h s e r F c i r t e m o r a B X B 2 M F I E r e z i m o n o c E X 3 D A F B d r a d n a t S r e p m a D r i A h s e r F c i r t e m o r a B X C 3 M F I E...

Reviews: