![Solair 11EER Series Installation Instructions Manual Download Page 35](http://html1.mh-extra.com/html/solair/11eer-series/11eer-series_installation-instructions-manual_1313277035.webp)
Manual 2100-723
Page
35 of 39
TABLE 14
Maximum ESP of Operation
Electric Heat Only
Values shown are for units equipped with standard 1"
throwaway filter or 1" washable filter.
Derate ESP by .15 for 2" pleated filters.
Models
240V-1
208V-1
240V-3
208V-3
460V-3
KW
Amps
BTUH
Amps
BTUH
Amps
BTUH
Amps
BTUH
Amps
BTUH
5
20.8
17065
18.1
12800
6
14.4
20500
12.5
15360
7.2
20500
9
21.7
30600
18.7
23030
10.8
30700
10
41.6
34130
36.2
25600
15
62.5
51250
54.0
38400
36.2
51200
31.2
38400
18.0
51200
18
43.3
61430
37.4
46060
20
83.2
68260
57.6
51200
TABLE 15
Electric Heat
Model
J42AC, J48AC
J60AC, J72AC
Outlet
FRONT
FRONT
Speed
High
Low
High
Low
-A0Z
-A05
-A10
-A15
-A20
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.40
-B0Z
-B06
-B09
-B15
-B18
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
-C0Z
-C09
-C15
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50