Solair 11EER Series Installation Instructions Manual Download Page 22

Manual 2100-723 

Page 

22 of 39

START UP

General

1.  Use separate service equipment to avoid cross 

contamination of oil and refrigerants.

2.  Use recovery equipment rated for R-410A 

refrigerant.

3.  Use manifold gauges rated for R-410A (800 

psi/250 psi low).

4.  R-410A is a binary blend of HFC-32 and HFC-125.
5.  R-410A is nearly azeotropic—similar to R-22 and 

R-12. Although nearly azeotropic, charge with 
liquid refrigerant.

6.  R-410A operates at 40-70% higher pressure 

than  R-22 and systems designed for R-22 cannot 
withstand this higher pressure.

7.  R-410A has an ozone depletion potential of zero, 

but must be reclaimed due to its global warming 
potential.

8.  R-410A compressors use polyol ester oil.
9.  Polyol ester oil is hygroscopic; it will rapidly absorb 

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used—even a deep 

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug 

compressor immediately after removal. Purge with 
small amount of nitrogen when inserting plugs.

Topping Off System Charge

If a leak has occurred in the system, Bard 
Manufacturing recommends reclaiming, evacuating 
(see criteria above) and charging to the nameplate 
charge. If done correctly, topping off the system charge 
can be done without problems.
With R-410A, there are no significant changes in the 
refrigerant composition during multiple leaks and 
recharges. R-410A refrigerant is close to being an 
azeotropic blend (it behaves like a pure compound 
or single component refrigerant). The remaining 
refrigerant charge, in the system, may be used after 
leaks have occurred and then “top-off” the charge by 
utilizing the pressure charts on the inner control panel 
cover as a guideline.

REMEMBER: 

When adding R-410A refrigerant, it must 

come out of the charging cylinder/tank as a liquid to 

avoid any fractionation, and to ensure optimal system 

performance. Refer to instructions for the cylinder that 

is being utilized for proper method of liquid extraction.

Safety Practices

1.  Never mix R-410A with other refrigerants.
2.  Use gloves and safety glasses. Polyol ester oils can 

be irritating to the skin, and liquid refrigerant will 
freeze the skin.

3.  Never use air and R-410A to leak check; the 

mixture may become flammable.

4.  Do not inhale R-410A—the vapor attacks 

the nervous system, creating dizziness, loss 
of coordination and slurred speech. Cardiac 
irregularities, unconsciousness and ultimate death 
can result from breathing this concentration.

5.  Do not burn R-410A. This decomposition produces 

hazardous vapors. Evacuate the area if exposed.

6.  Use only cylinders rated DOT4BA/4BW 400.
7.  Never fill cylinders over 80% of total capacity.
8.  Store cylinders in a cool area, out of direct 

sunlight.

9.  Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge 

lines or cylinders. R-410A expands significantly at 
warmer temperatures. Once a cylinder or line is full 
of liquid, any further rise in temperature will cause 
it to burst.

Important Installer Note

For improved start up performance, wash the indoor 
coil with a dishwashing detergent.

High Pressure Switch

All J**AC wall-mounted air conditioner series models 
are supplied with a remote reset for the high and low 
pressure switch. If tripped, the pressure switch may be 
reset by turning the thermostat off then back on again. 
High pressure switch settings: Opens 650 +/– 15 PSI, 
Closes 520 +/– 15 PSI.

Three Phase Scroll Compresser Start 

Up Information

Scroll compressors, like several other types of 
compressors, will only compress in one rotational 
direction. Direction of rotation is not an issue with 
single phase compressors since they will always start 
and run in the proper direction.

These units require R-410A refrigerant and 

polyol ester oil.

Summary of Contents for 11EER Series

Page 1: ...1EER WA SERIES WALL MOUNT AIR CONDITIONER Models INSTALLATION INSTRUCTIONS J42AC A J42AC B J42AC C J48AC A J48AC B J48AC C J60AC A J60AC B J60AC C J72AC A J72AC B J72AC C Manual 2100 723 Supersedes NE...

Page 2: ...ownout Protection with Adjustment 25 Pressure Service Ports 25 Service 26 Troubleshooting Nidec SelecTech Series ECM Motors 26 If the Motor is Running 26 If the Motor is Not Running 26 Model SelecTech...

Page 3: ...rigeration and Air Conditioning Engineers Inc 1791 Tullie Circle N E Atlanta GA 30329 2305 Telephone 404 636 8400 Fax 404 321 5478 NFPA National Fire Protection Association Batterymarch Park P O Box 9...

Page 4: ...ad before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they...

Page 5: ...ed with installations not requiring a return air duct The spacing between louvers on the grille shall not be larger than 5 8 Any grille that meets with 5 8 louver criteria may be used It is recommende...

Page 6: ...ack of the filter tray 4 Re install the filter support brackets into the upper slots at the back of the filter tray see Figure 7 5 Re install the four 4 screws into the lower screw holes on the filter...

Page 7: ...r amounts based on the slide adjustment setting All capacity efficiency and cost of operation information is based upon the fresh air blank off plate in place The blank off plate is available upon req...

Page 8: ...condensate drainage A plastic drain hose extends from the drain pan in the upper section of the unit and extends down to the unit base An opening is supplied towards the back of the unit base for the...

Page 9: ...applicable installation codes may limit this cabinet to installation only in a single story structure Thermostat or Indoor Temperature Sensor Placement The location and installation of the thermostat...

Page 10: ...and mark bolt hole locations and bottom mounting bracket location Install bottom mounting bracket with field supplied fasteners to wall if it is to be used optional Bracket must be level and installed...

Page 11: ...2AC 1 4 0 FIGURE 11 Vent Installation Removal Clearance Required 20 750 2 000 37 250 17 750 45 000 MIS 4042 KEEP AREA CLEAR FOR 45 VENT SHOWN OUTSIDE OF UNIT CLEARANCE NEEDED ON LEFT OR RIGHT SIDE OF...

Page 12: ...Built In Low Voltage Electrical Entrance J A C I K D 2 250 H 1 375 Location Flashing Top Rain Shipping Side Wall Mounting Brackets Built In 375 B E O M N T S S S S S L R 375 TYP Width W Depth D Height...

Page 13: ...ning and Hole Location View Supply Opening Return Opening UNITS REQUIRED DIMESIONS A B C D E F G J42AC J48AC UNITS REQUIRED DIMESIONS TO MAINTAIN 1 4 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS 30 1 2 10...

Page 14: ...OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3...

Page 15: ...ACH TO BOTTOM PLATE OF WALL 1 000 CLEARANCE ALL AROUND DUCT ATTACH TO TOP PLATE OF WALL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME W...

Page 16: ...WERED GRILLE RAISED FLOOR RETURN AIR OUTSIDE SPACE RETURN AIR RAFTERS RAFTERS WALL OUTSIDE WALL SUPPLY AIR DUCT FALSE WALL OUTSIDE WALL OUTSIDE W GRILLE SURFACE RETURN AIR WALL FLASHING RAIN FLASHING...

Page 17: ...IRE SHIELD FIELD WIRE SHIELD FRONT VIEW USE CONDUIT WHEN FIELD WIRES COME IN THROUGH THE BACK RIGHT SIDE VIEW FIGURE 18 High Voltage Connections the number of field power circuits required for the var...

Page 18: ...n the relay Unit Shutdown Feature Standard on All Models The RT terminal is the 24VAC transformer output and the R terminal is the 24VAC hot terminal for the operation of the equipment RT and R are co...

Page 19: ...Thermostats Part Number Predominate Features 8403 057 TH3110D1040 1 stage Cool 1 stage Heat Electronic Non Programmable Auto or Manual changeover 8403 059 TH5220D1219 U 2 stage Cool 2 stage Heat Elect...

Page 20: ...cupied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidification must be configured for No Economizer for YO D to be active for humidity control 4 Fa...

Page 21: ...CO2 control signal for modulating ventilation control Optional for ECON Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while bl...

Page 22: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utilize...

Page 23: ...ion Service Hints 1 Caution owner operator to maintain clean air filters at all times and also not to needlessly close off supply and return air registers This reduces airflow through the system which...

Page 24: ...led vent package it will be plugged in but the jumper plug will also be tethered next to the connection for troubleshooting purposes if necessary Compressor Control Module The compressor control modul...

Page 25: ...timers can be set by DIP switches in order to delay signaling a power brownout for a specific length of time after compressor contactor is energized This allows the compressor a time period to start e...

Page 26: ...3302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back a...

Page 27: ...tput 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground at the L L1 G N L2 connections then continue with the Model SelecTech Communic...

Page 28: ...cleaning or to service the outdoor fan first remove the side grilles 3 The fan shroud sides can then be removed for ease of access to the coil and the back side of the shroud by removing the seven 7...

Page 29: ...85 72 Low Side High Side 135 333 138 357 140 382 142 407 144 434 146 461 148 489 150 519 152 549 155 580 157 612 J48AC 75 62 Low Side High Side 128 331 131 352 133 374 135 398 137 422 138 448 140 474...

Page 30: ...9 633 85 72 Low Side High Side 127 331 129 349 131 368 134 390 136 415 139 441 141 470 143 501 146 534 148 569 151 608 J48AC 75 62 Low Side High Side 122 320 123 341 125 365 127 388 129 412 132 438 13...

Page 31: ...Ckt C Ckt A Ckt B Ckt C J42AC A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 31 31 57 83 109 50 50 60 90 125 8 8 6 4 2 10 10 10 8 6 57 57 26 52 60 60 30 60 6 6 10 6 10 10 10 10 J42AC B00 B0Z B0...

Page 32: ...page 34 for the corresponding airflow of each tap Set the unit duct static based on the highest airflow that the unit will run at NOTE Be sure to adjust the system static or blower speed to maintain a...

Page 33: ...s used when Balanced Climate is called for by energizing the Y1 terminal of the low voltage terminal block with 24VAC Speed tap 2 is overridden if taps 3 4 or 5 are energized Speed Tap 3 Default LO Co...

Page 34: ...1655 1555 1785 1685 1870 1780 0 25 1615 1520 1750 1645 1835 1745 0 30 1575 1485 1715 1610 1800 1710 0 40 1485 1405 1635 1540 1730 1635 050 1390 1325 1550 1475 1655 1560 J60AC 0 00 1540 1480 1960 1870...

Page 35: ...5 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 15 62 5 51250 54 0 38400 36 2 51200 31 2 38400 18 0 51200 18 43 3 61430 37 4 46060 20 83 2 68...

Page 36: ...f 39 TABLE 16 Vent and Control Options All Models Part Number Description CMC 32 Start Kit 230V 1 Phase X CMA 39 LAC On Off X FAD NE5 Fresh Air Damper No Exhaust X ECONWD 5 Economizer Bldg Equipment E...

Page 37: ...HWA42CD B09 X EHWA42C B15 X EHWA42C B18 X EHWA42C C09 X EHWA42C C15 X X EHWA48C A05 X X EHWA48C B15 X EHWA48C B18 X X X EHWA48C C09 X EHWA60C A10 X EHWA60C A15 X EHWA60C A20 X EHWA60C B06 X EHWA60C B0...

Page 38: ...Manual 2100 723 Page 38 of 39 GRAPH 1 J42AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 2 J48AC FAD NE5 W O Exhaust Ventilation Delivery...

Page 39: ...Manual 2100 723 Page 39 of 39 GRAPH 3 J60AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 4 J72AC FAD NE5 W O Exhaust Ventilation Delivery...

Reviews: