TABLE 8 

Cooling Pressure – Standard Airflow

Air Temperature Entering Outdoor Coil °F

Low side pressure ± 4 PSIG                                                         
High side pressure ± 10 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge 
being in the system, the charge should be removed and system evacuated and recharged to serial plate charge weight.

NOTE:

  Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check 

condenser fan wiring. See “Condenser Fan Operation”.

* Operating at these conditions would be outside the compressor operating envelope and is not recommended.

Model

Return Air Temp 

(DB/WB)

Pressure

75

80

85

90

95

100

105

110

115

120

125

131

J42AC

75/62

Low Side

High Side

122
314

124
336

126
360

128
383

130
409

132
434

134
460

136
488

137
517

140
546

142
576

145
613

80/67

Low Side

High Side

130
322

133
345

135
369

137
393

139
419

141
445

143
472

145
501

147
530

150
560

152
591

155
629

85/72

Low Side

High Side

135
333

138
357

140
382

142
407

144
434

146
461

148
489

150
519

152
549

155
580

157
612

--*

J48AC

75/62

Low Side

High Side

128
331

131
352

133
374

135
398

137
422

138
448

140
474

142
502

144
530

146
561

148
592

150
631

80/67

Low Side

High Side

137
339

140
361

142
384

144
408

146
433

148
459

150
486

152
515

154
544

156
575

158
607

160
647

85/72

Low Side

High Side

142
351

145
374

147
397

149
422

151
448

153
475

155
503

157
533

159
563

161
595

164
628

--*

J60AC

75/62

Low Side

High Side

127
326

129
348

131
371

133
395

134
420

136
446

137
472

139
499

140
527

142
556

143
586

145
622

80/67

Low Side

High Side

136
334

138
357

140
381

142
405

143
431

145
457

147
484

149
512

150
540

152
570

153
601

155
638

85/72

Low Side

High Side

141
346

143
369

145
394

147
419

148
446

150
473

152
501

154
530

155
559

157
590

158
622

--*

J72AC

75/62

Low Side

High Side

119
334

121
356

122
379

123
403

125
428

127
453

129
481

131
509

133
538

134
567

136
599

137
638

80/67

Low Side

High Side

127
343

129
365

131
389

132
413

134
439

136
465

138
493

140
522

142
552

143
582

145
614

--*

85/72

Low Side

High Side

131
355

134
378

136
403

137
427

139
454

141
481

143
510

145
540

147
571

148
602

150
635

--*

Summary of Contents for 11EER Series

Page 1: ...1EER WA SERIES WALL MOUNT AIR CONDITIONER Models INSTALLATION INSTRUCTIONS J42AC A J42AC B J42AC C J48AC A J48AC B J48AC C J60AC A J60AC B J60AC C J72AC A J72AC B J72AC C Manual 2100 723 Supersedes NE...

Page 2: ...ownout Protection with Adjustment 25 Pressure Service Ports 25 Service 26 Troubleshooting Nidec SelecTech Series ECM Motors 26 If the Motor is Running 26 If the Motor is Not Running 26 Model SelecTech...

Page 3: ...rigeration and Air Conditioning Engineers Inc 1791 Tullie Circle N E Atlanta GA 30329 2305 Telephone 404 636 8400 Fax 404 321 5478 NFPA National Fire Protection Association Batterymarch Park P O Box 9...

Page 4: ...ad before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they...

Page 5: ...ed with installations not requiring a return air duct The spacing between louvers on the grille shall not be larger than 5 8 Any grille that meets with 5 8 louver criteria may be used It is recommende...

Page 6: ...ack of the filter tray 4 Re install the filter support brackets into the upper slots at the back of the filter tray see Figure 7 5 Re install the four 4 screws into the lower screw holes on the filter...

Page 7: ...r amounts based on the slide adjustment setting All capacity efficiency and cost of operation information is based upon the fresh air blank off plate in place The blank off plate is available upon req...

Page 8: ...condensate drainage A plastic drain hose extends from the drain pan in the upper section of the unit and extends down to the unit base An opening is supplied towards the back of the unit base for the...

Page 9: ...applicable installation codes may limit this cabinet to installation only in a single story structure Thermostat or Indoor Temperature Sensor Placement The location and installation of the thermostat...

Page 10: ...and mark bolt hole locations and bottom mounting bracket location Install bottom mounting bracket with field supplied fasteners to wall if it is to be used optional Bracket must be level and installed...

Page 11: ...2AC 1 4 0 FIGURE 11 Vent Installation Removal Clearance Required 20 750 2 000 37 250 17 750 45 000 MIS 4042 KEEP AREA CLEAR FOR 45 VENT SHOWN OUTSIDE OF UNIT CLEARANCE NEEDED ON LEFT OR RIGHT SIDE OF...

Page 12: ...Built In Low Voltage Electrical Entrance J A C I K D 2 250 H 1 375 Location Flashing Top Rain Shipping Side Wall Mounting Brackets Built In 375 B E O M N T S S S S S L R 375 TYP Width W Depth D Height...

Page 13: ...ning and Hole Location View Supply Opening Return Opening UNITS REQUIRED DIMESIONS A B C D E F G J42AC J48AC UNITS REQUIRED DIMESIONS TO MAINTAIN 1 4 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS 30 1 2 10...

Page 14: ...OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3...

Page 15: ...ACH TO BOTTOM PLATE OF WALL 1 000 CLEARANCE ALL AROUND DUCT ATTACH TO TOP PLATE OF WALL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME W...

Page 16: ...WERED GRILLE RAISED FLOOR RETURN AIR OUTSIDE SPACE RETURN AIR RAFTERS RAFTERS WALL OUTSIDE WALL SUPPLY AIR DUCT FALSE WALL OUTSIDE WALL OUTSIDE W GRILLE SURFACE RETURN AIR WALL FLASHING RAIN FLASHING...

Page 17: ...IRE SHIELD FIELD WIRE SHIELD FRONT VIEW USE CONDUIT WHEN FIELD WIRES COME IN THROUGH THE BACK RIGHT SIDE VIEW FIGURE 18 High Voltage Connections the number of field power circuits required for the var...

Page 18: ...n the relay Unit Shutdown Feature Standard on All Models The RT terminal is the 24VAC transformer output and the R terminal is the 24VAC hot terminal for the operation of the equipment RT and R are co...

Page 19: ...Thermostats Part Number Predominate Features 8403 057 TH3110D1040 1 stage Cool 1 stage Heat Electronic Non Programmable Auto or Manual changeover 8403 059 TH5220D1219 U 2 stage Cool 2 stage Heat Elect...

Page 20: ...cupied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidification must be configured for No Economizer for YO D to be active for humidity control 4 Fa...

Page 21: ...CO2 control signal for modulating ventilation control Optional for ECON Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while bl...

Page 22: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utilize...

Page 23: ...ion Service Hints 1 Caution owner operator to maintain clean air filters at all times and also not to needlessly close off supply and return air registers This reduces airflow through the system which...

Page 24: ...led vent package it will be plugged in but the jumper plug will also be tethered next to the connection for troubleshooting purposes if necessary Compressor Control Module The compressor control modul...

Page 25: ...timers can be set by DIP switches in order to delay signaling a power brownout for a specific length of time after compressor contactor is energized This allows the compressor a time period to start e...

Page 26: ...3302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back a...

Page 27: ...tput 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground at the L L1 G N L2 connections then continue with the Model SelecTech Communic...

Page 28: ...cleaning or to service the outdoor fan first remove the side grilles 3 The fan shroud sides can then be removed for ease of access to the coil and the back side of the shroud by removing the seven 7...

Page 29: ...85 72 Low Side High Side 135 333 138 357 140 382 142 407 144 434 146 461 148 489 150 519 152 549 155 580 157 612 J48AC 75 62 Low Side High Side 128 331 131 352 133 374 135 398 137 422 138 448 140 474...

Page 30: ...9 633 85 72 Low Side High Side 127 331 129 349 131 368 134 390 136 415 139 441 141 470 143 501 146 534 148 569 151 608 J48AC 75 62 Low Side High Side 122 320 123 341 125 365 127 388 129 412 132 438 13...

Page 31: ...Ckt C Ckt A Ckt B Ckt C J42AC A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 31 31 57 83 109 50 50 60 90 125 8 8 6 4 2 10 10 10 8 6 57 57 26 52 60 60 30 60 6 6 10 6 10 10 10 10 J42AC B00 B0Z B0...

Page 32: ...page 34 for the corresponding airflow of each tap Set the unit duct static based on the highest airflow that the unit will run at NOTE Be sure to adjust the system static or blower speed to maintain a...

Page 33: ...s used when Balanced Climate is called for by energizing the Y1 terminal of the low voltage terminal block with 24VAC Speed tap 2 is overridden if taps 3 4 or 5 are energized Speed Tap 3 Default LO Co...

Page 34: ...1655 1555 1785 1685 1870 1780 0 25 1615 1520 1750 1645 1835 1745 0 30 1575 1485 1715 1610 1800 1710 0 40 1485 1405 1635 1540 1730 1635 050 1390 1325 1550 1475 1655 1560 J60AC 0 00 1540 1480 1960 1870...

Page 35: ...5 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 15 62 5 51250 54 0 38400 36 2 51200 31 2 38400 18 0 51200 18 43 3 61430 37 4 46060 20 83 2 68...

Page 36: ...f 39 TABLE 16 Vent and Control Options All Models Part Number Description CMC 32 Start Kit 230V 1 Phase X CMA 39 LAC On Off X FAD NE5 Fresh Air Damper No Exhaust X ECONWD 5 Economizer Bldg Equipment E...

Page 37: ...HWA42CD B09 X EHWA42C B15 X EHWA42C B18 X EHWA42C C09 X EHWA42C C15 X X EHWA48C A05 X X EHWA48C B15 X EHWA48C B18 X X X EHWA48C C09 X EHWA60C A10 X EHWA60C A15 X EHWA60C A20 X EHWA60C B06 X EHWA60C B0...

Page 38: ...Manual 2100 723 Page 38 of 39 GRAPH 1 J42AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 2 J48AC FAD NE5 W O Exhaust Ventilation Delivery...

Page 39: ...Manual 2100 723 Page 39 of 39 GRAPH 3 J60AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 4 J72AC FAD NE5 W O Exhaust Ventilation Delivery...

Reviews: