COMMISSIONING
All water heaters are tested and adjusted before dispatch from the factory, however further adjustments may
become necessary because of local conditions.
Note:
If this water heater is installed as part of a multiple installation, i.e. in a bank of water heaters, it will be
necessary to isolate the other water heaters and commission the water heaters one at a time. However, all
the water heaters will need to be operating during the checking of the gas pressure.
TO TURN ON THE WATER HEATER
Open all of the hot taps in the house (don‟t forget the shower).
Open the cold water isolation valve fully at the inlet to the solar water heater.
Open the solar heated water isolation valve fully at the inlet to the in-series gas booster.
Air will be forced out of the taps.
Close each tap as water flows freely from it.
Check the pipe work for leaks.
Open the gas isolation valve fully.
Check the gas pipe work for leaks.
Plug in the water heater at the power outlet and switch on the electrical supply.
Open a hot tap.
The water heater will operate automatically.
Check to ensure the flow from each connected hot tap is sufficient to operate the water heater.
The minimum operating flow rate is 2.5 L / min (20L models) or 2.0 L / min (27L models).
Check and if required adjust the preset outlet temperature setting of the water heater.
Refer to
“Preset Outlet Temperature Setting”
on page 34.
The automatic water governor incorporated in the water heater is not adjustable.
To complete the installation, it is necessary to check the gas supply pressure at the inlet to the water heater
(refer to
on page 28), the minimum test point pressure and the maximum test point
pressure (refer to
on page 30).
Explain to the householder or a responsible officer the functions and operation of the water heater and the
solar water heater system.
Warning:
Upon completion of the installation and commissioning of the water heater, leave this guide
with the householder or a responsible officer.
DO NOT
leave this guide inside of the cover of the water
heater, as it may interfere with the safe operation of the water heater or ignite when the water heater is
turned on.
GAS INLET PRESSURE
IMPORTANT - CHECK
the gas supply pressure at the inlet to the water heater with the water heater and all
other gas burning appliances in the premises operating (burners alight). The minimum gas supply pressure
is:
Natural Gas
1.13 kPa
Propane
2.75 kPa
If this minimum cannot be achieved, it may indicate the meter or the gas line to the water heater is
undersized. It is important to ensure that an adequate gas supply pressure is available to the water heater
when other gas burning appliances, on the same gas supply, are operating.