3.1.3 Connecting the power supply
1.
Connect the FG-200 to a 24 V DC power supply.
2.
Use different or redundant power supplies for redundant FG-200s.
3.
Turn on the power supply. The boot process takes approx. 50 seconds. For indication
of proper operation of a FG-200 acting in non-redundant mode or as primary device
in redundant mode refer to
.
The supply voltage (18 VDC .... 32 VDC) is connected by a 3-pole terminal block. The power
supply is connected to the plug connector via flexible wires with a cross section of 0.75 to
1.5 mm². The ground connection wire must have a cross section of 1.5 mm².
Pin
Signal
Description
1
GND
Ground
2
Functional earth
3
L+
Positive supply voltage
CAUTION
The Functional Earth (FE) connection of the device has to be connected at low
inductance with the Protective Earth (PE) of the system.
Note
As indicated in the connection diagram, the power can be applied alternatively
by a special DIN rail connector (Rail Power Supply). For further information
contact Softing Industrial Automation.