FG-200 HSE/FF Modbus - Qui ck Sta rtup Gui de
22
© Softing Industrial Automation GmbH
3.1.8 Powering up the device
Turn on the power supply. The boot process takes a few seconds. For indication of proper
operation of a FG-200 refer to
.
3.1.9 Adding a second FG-200 for redundancy
For adding a second FG-200 to an already commissioned FG-200 that is operating in the
role "Primary, no backup", the following steps are required:
1.
Set the IP configuration (IP address and subnet mask) of the second FG-200 using the
same IP subnet as the primary device (see
).
2.
Connect the H1 links to the terminal blocks of the H1 interfaces. Make sure to connect
each H1 link to the same channel (CH 1 .. CH 4) on both FG-200s.
3.
Connect the second FG-200 to the Ethernet switch or hub.
4.
Connect both RDL interfaces as mentioned in Section
5.
Connect the second FG-200 to a 24 V DC power supply. Use different or redundant
power supplies for redundant FG-200s.
6.
After turning on the power supply the boot process takes approx. 50 seconds.
7.
The second FG-200 will take over the configuration data from the primary device and
will start operation in the role "secondary". For more details about proper operation
as a secondary device see also the
.
Hint
Refer to Section
for more information on the
redundancy concept.