![Softing echolink one2PROFINET Instruction Manual Download Page 43](http://html1.mh-extra.com/html/softing/echolink-one2profinet/echolink-one2profinet_instruction-manual_1312387043.webp)
Hardware ports, switches and LEDs
Softing Industrial Automation GmbH
43
echolink one2PROFINET V. 1.0
15.1.15
9.2.2
Connector supply voltage and Debug-interface
Pin No.
Name
Function
1
UB (Pwr)
10..33 V supply voltage / DC
2
0 V (Pwr)
0 V supply voltage / DC
3
Rx-Debug
Receive signal Debug -> only for Development. Not
required in normal operation.
4
Tx-Debug
Send signal Debug -> only for Development. Not
required in normal operation.
Pin assignment X2 (4-pole screw-plug connector, on the bottom side, at the back)
9.2.3
PROFINET-connector
The plugs (labeled: RJ45 PROFINET-IO) for the connection to PROFINET are available on the
bottom side of the device.
Pin assignment X3 P1 (RJ45 up front, i. e. which is located closer to the front panel)
Pin No.
Name
Function
1
TD+
Transmission line +
2
TD-
Transmission line -
3
RD+
Receive line +
4
5
6
RD-
Receive line -
7
8
Pin assignment X3 P2 (RJ45 at the back, i. e. which is located closer to the DIN-rail)
Pin No.
Name
Function
1
TD+
Transmission line +
2
TD-
Transmission line -
3
RD+
Receive line +
4
5
6
RD-
Receive line -
7
8
9.2.4
Power supply
The device must be powered with 10-33 VDC, The voltage supply is made through the 4-pole
screw-plug connector at the device’s bottom side.
Please note that the devices of the series echolink one should not be operated with AC voltage.
9.3 LEDs
The Gateway echolink one2PROFINET features 10 LEDs with the following significance:
LED (PROFINET) Power
green
Supply voltage PROFINET (total device)
LED Link / Act. P1
green
Ethernet-link pulse found / network data traffic Port 1
LED Link / Act. P2
green
Ethernet-link pulse found / network data traffic Port 2
LED (PROFINET) State
red/green
Interface state Profinet
LED Power
green
Supply voltage serial interface
LED State
red/green
Interface condition serial interface
LEDs 1 / 2 / 4 / 8 (Error No. / Select ID) green
Binary display of the Error number
9.3.1
LED "(PROFINET) Power"