Implemented protocols in echolink one
8.8.3.6
Example: Preset single register FC6
Configuration
SPS sends to echolink one
01 00 00 00 00 00 00
FF23
00 FF 00 00 00 00 00 FF 00 00 00 00 00 00 00 00 00 00 00 00 00 ...
echolink one sends Modbus RTU request
[01] [06] [00] [05] [ff] [23] [99] [e2]
Modbus Slave sends response
[01] [06] [00] [05] [ff] [23] [99] [e2]
Storage content of Modbus Slave after Response:
8.8.3.7
Example: Force multiple coils FC15
Configuration
Fieldbus Master sends:
0E 00 FF 05 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00...
echolink one sends request:
[01] [0f] [00] [02] [00] [0a] [02] [ff] [05] [65] [29]
Modbus Slave sends response:
[01] [0f] [00] [02] [00] [0a] [74] [0c]
Storage content of Modbus Slave after response: