Technical Manual MIVI 8001
Ref. 128-41/5
10
2.2.1. Elbow mounting
2.2.2. Plane side mounting
2.2.3. On pot mounting, for small flow rates, or pilot plant
See fig.3.
2.2.4. Special mountings
2.2.5. Replacement cap
2.3. Practical
advices
The flange is welded on a right angle tee as indicated in
fig.1.
•
The minimal pipe diameter is of 32 mm.
•
The flange and the pipe axes have to be superjacent.
•
The flow direction is as indicated on fig.1 (unless for
fibrous fluids where the flow is inverted and the rod
protector removed.
A free area of at least 150 mm length is necessary.
•
The flange is welded as indicated on fig.2.
•
The free area around the vibrating rod has to be at
least
∅
40, 150 mm length.
•
In order to avoid parasitic vibrations, the plate where
the flange is welded must be thicker than 5 mm.
The small sensor size allows numerous personalization
of its fitting according to the user's requirements.
Consult your Distributor.
Each mounting flange is provided with the
corresponding cap and its accessories (screws and
gaskets). It allows the installation working when the
sensor has to be removed.
Torque at the mounting screws: 9 N.m
±
1 at the M6
×
100
screws, or 22 N.m
±
1 at the M8 screws (for the high
pressure design).
Notes:
Each sensor is equipped with a guard tube in order to
protect the vibrating rod. In most cases, it is designed
according to the application, and has not to be removed,
unless when it disturbs the sensor operation: on pot
mounting, sanitary use, very viscous and fibrous fluids,
where a replacement ring is used.
Mounting flange,
welded
150 mm
5 mm
int.
∅
32
mm
mini
Fig. 1
∅
40 mm mini
150 mm
17
Mounting flange,
welded
Fig. 2
¼
gas
Fig.3
On circulation pot
Weight : 5,6
kg
Earth terminal