SOFAR 7K~10.5KTLM-G3
User manual
Copyright © Shenzhen SOFAR SOLAR Co., Ltd
- 50 -
If an Earth Fault Alarm occurs, the fault will be displayed on the LCD screen,
the red light will be on, and the fault can be found in the history of the fault. For
the machine installed with Wi-Fi/GPRS, the alarm information can be seen on
the corresponding monitoring website, and can also be received by the APP on
the mobile phone.
Table 7-1 Event list
Code
Name
Description
Solution
ID001
GridOVP
The grid voltage is too
high
If the alarm occurs occasionally, the
possible cause is that the electric grid
is abnormal occasionally. Inverter will
automatically
return
to
normal
operating status when the electric
grid’s back to normal.
If the alarm occurs frequently, check
whether the grid voltage/frequency is
within the acceptable range. If yes,
please check the AC circuit breaker
and AC wiring of the inverter.
If the grid voltage/frequency is NOT
within the acceptable range and AC
wiring is correct, but the alarm occurs
repeatedly, contact technical support
to change the grid over-voltage,
under-voltage,
over-frequency,
under-frequency protection points
after obtaining approval from the local
electrical grid operator.
ID002
GridUVP
The grid voltage is too
low
ID003
GridOFP
The grid frequency is
too high
ID004
GridUFP
The grid frequency is
too low
ID005
GFCI
Charge Leakage Fault
Internal faults of inverter, switch OFF
inverter, wait for 5 minutes, then
switch ON inverter. Check whether the
problem is solved.
If no, please contact technical support.
ID006
OVRT
OVRT
function
is
faulty
ID007
LVRT
LVRT function is faulty
ID008
IslandFault
Island protection error
ID009
GridOVPInstant1
Transient overvoltage
of grid voltage 1
ID010
GridOVPInstant2
Transient overvoltage
of grid voltage 2
ID011
VGridLineFault
Power grid line voltage
error
ID012
InvVoltFault
Inverter
voltage
overvoltage
ID017
HwADErrIGrid
Power
grid
current