SOFAR 25~50KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 52 -
019
000
IEC EN61727
020
000
Korea
021
000
Sweden
022
000
Europe General
Table 7-1 Country code setting
For The Australian Market:
For compliance with AS/NZS 4777.2:2020 please select from
002-000 Australia A (Australia Region A)
002-008 Australia B (Australia Region B)
002-009 Australia C (Australia Region C)
Please contact your local grid operator for which option to select
Note: By selecting 002-000 Australia A, 002-008 Australia B or 002-009 Australia C
the power quality response mode and grid protection settings will be reset to their
default values for Australia Region A, B, C respectively.
Default grid settings for different regions are shown in the following table:
Protective function
Protective function
limit
Trip delay time
Maximum
disconnection time
Undervoltage 2(V<<)
70V
1s
2s
Undervoltage 1(V<)
180V
10s
11s
Overvoltage 1(V>)
265V
1s
2s
Overvoltage 2(V>)
275V
-
0.2s
Region
Australia A
Australia B
Australia C
New Zealand
Under-
frequency 1
(F<)
Protective
function limit
value
47Hz
47Hz
45Hz
45Hz
Trip
delay
time
1s
1s
5s
1s
Maximum
disconnection
time
2s
2s
6s
2s
Over-
frequency 1
(F>)
Protective
function limit
value
52Hz
52Hz
55Hz
55Hz
Trip
delay
time
-
-
-
-
Maximum
disconnection
time
0.2s
0.2s
0.2s
0.2s
Default volt-watt settings for different regions are shown in the following table: