4.Electrical Connection
Outlines of this Chapter
This section introduces the electrical connection for the product. Please read the
information carefully, it may helpful to understand the grounding wiring, DC input
connection, AC output connection and communication connection.
Caution:
Before performing electrical connections, ensure the DC switch is OFF and AC
circuit breaker is OFF. Waiting 5 minutes for the capacitor to be electrically
discharged.
Installation and maintenance should be done by certified electrical
engineer
Attention
Before the electrical connection, use opaque material to cover the PV
modules or disconnect PV string DC switch. PV arrays will produce
dangerous voltage if it is exposure under sun
Danger
For this product, the open circuit voltage of PV strings should not
greater 1100V
Note
The connected panel must meet the standard IEC61730A
。
String
Model
IscPV(maximum)
Maximum output current
(A)
SOFAR 25KTLX-G3
3*50A
42.4A
SOFAR 30KTLX-G3
51.5A
SOFAR 30KTLX-G3-A
45.3A
SOFAR 33KTLX-G3
56A