SOFAR 15~24KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 55 -
grid information.
“Enter”
1Enter setting
“OK”
1 Set Time
2 Event List
2 Clean Energy
“Up”
↑
3 System Info
“Up”
↑
3 Clean Events
“Down
↑
4 Display Time
“Down”
↑
......
5 Software Update
10 Set Reflux P
“OK”
Input password!
“OK”
****
Input 0001
0001
“OK”
Anti Reflux Control
Hard Anti Reflux Control
Anti Reflux Control
“OK”
Enable
“OK”
*.**KW
Input the allowable export
power
Disable
Hard Anti Reflux
Control
“OK”
Enable
“OK”
*.**KW
Input the allowable export
power
Disable
Press
“
Up
”
or
“
Down
”
to change the value of the first digit. Press
“
OK
”
to switch to second digit.
Press
“
Up
”
or
“
Down
”
to change the value of the second digit. After inputting all digit press
“
OK
”
to
confirm.
Note
:
When enabling the Hard Anti Reflux Control and Anti Reflux Control at the
same time, generation limit control will be enabled. note that the allowable export
power of soft limit should be smaller than that of the hard limit. After the setting is
successful, the off-grid time after the communication failure of the meter is
changed from 5S to 15-20S.
11. Logic interface
Enable or disable logical interfaces. It is use for below standard Australia
(AS4777), Europe General (50549), German (4105).
12. IV Curve Scan
Shadow scanning, when the component is blocked or abnormal, causing
multiple power peaks, by enabling this function, the peak point of maximum power
can be tracked.