SUNSYS H50
- Ref.: IOMSUNHMXX05-GB 01
ENGLISH
8. MENU
8.3. SELF-TEST
WARNING!
This menu is available only if Italy is set as Country.
During each test the inverter switched off and on.
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
6.3-1
Italy self test view
Italy Selftest
& History
UH =264.5
Next Enter
UL =195.5
Next Enter
FH =51.5
Next Enter
FL =47.50
Next Enter
UH =253.0
Next Enter
UL =192.0
Next Enter
UH:264.5/264.5 V
Pass 215/200 ms
UL:195.5/195.5 V
Pass 415/400 ms
FH:51.50/51.50 V
Pass 1004/1000ms
FL:47.50/47.50 V
Pass 4009/4000ms
UH:253.0/253.0 V
Pass 3015/3000ms
UH:192.0/192.0 V
Pass 215/200 ms
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
Count Down
60 sec
Count Down
60 sec
Count Down
60 sec
Count Down
60 sec
Count Down
60 sec
Count Down
60 sec
SEL
ENT
Italy Selftest
& History
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
SEL
ENT
UH:264.5/264.5 V
Pass 215/200 ms
UL:195.5/195.5 V
Pass 415/400 ms
FH:51.50/51.50 V
Pass 1004/1000ms
FL:47.50/47.50 V
Pass 4009/4000ms
UH:253.0/253.0 V
Pass 3015/3000ms
UH:192.0/192.0 V
Pass 215/200 ms
SEL
ENT
Italy Selftest
& History
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
3 sec
Startup
procedure