24
SUNSYS H50
- Ref.: IOMSUNHMXX05-GB 01
24
9. MESSAGES
A30: Bus
Unbalance
1. Not totally independent or parallel between inputs
2. PV Array short to Ground
3. Driver for boost is defective or disconnected
4. Detection circuit malfunction
1. Check the input connections
2. Check the PV Array insulation
3. Check the driver curcuit for boost inside the inverter
4. Check the detection circuit inside the inverter
A31: Bus_P Over
Volt Rating
1. Problems with wiring of strings
2. String short-circuiting to earth
3. Internal control circuits not working
1. Check the parallel string setup connected to the inverter
2. Check the system
3. Contact the technician
A33: Bus_N Over
Volt Rating
1. Problems with wiring of strings
2. String short-circuiting to earth
3. Internal control circuits not working
1. Check the parallel string setup connected to the inverter
2. Check the system
3. Contact the technician
A35: Bus Volt
Over Rating
1. Driver for boost is defective
2. Voc of PV array is over 1000Vdc
3. Surge occurs during operation
4. Detection circuit malfunction
1. Check the driver curcuit for boost inside the inverter
2. Modify the solar array setting, and make the
Voc less than 1000Vdc
3. N/A
4. Check the detection circuit inside the inverter
A36:Output Curr
Transient Over
1. Surge occurs during operation
2. Driver for inverter stage is defective
3. Switching device is defective
4. Detection circuit malfunction
1. N/A
2. Check the driver circuit in inverter stage
3. Check all switching devices in inverter stage
4. Check the detect circuit inside the inverter
A37: AC Curr
Over Rating
1. AC grid overvoltage
2. Internal control circuits not working
1. Switch off/switch on again
2. Contact the technician
A45: HW OOCP
1. WB1 WB2 misconnection.
2. Detection circuit malfunction
1. Check the connection of WB1 and WB2.
2. Check the detection circuit inside the inverter
A50:Zero Cross
Circuit Fail
The detection circuit for synchronal signal malfunction
Check the detection circuit for synchronal signal
inside the inverter
A56:Hardware
Incompatibility
Firmware version incorrect
Update the firmware
A60: DC Curr
Over Rating
1. Switching device in boost is defective
2. Driver for boost is defective
3. Input current detection circuit malfunction
1. Check all switching device in boost
2. Check the driver curcuit for boost inside the inverter
3. Check input current detection circuit
A70: DC Curr
Transient Over
1. Switching device in boost is defective
2. Driver for boost is defective
3. Input current detection circuit malfunction
1. Check all switching device in boost
2. Check the driver curcuit for boost inside the inverter
3. Check input current detection circuit