47
MASTERYS BC
100-120 kVA - Ref.: IOMMASBCXX07-EN 05
ENGLISH
10. TECHNICAL SPECIFICATIONS
1. 360 V with Pout = 90% Pn.
2. Initial Condition Pout ≤ 80% Pn
3. @ Battery Fully Discharged. Call SOCOMEC support service.
4. @ Battery Fully Charged. Call SOCOMEC support service.
Models
100
120
Electrical specifications - Input
Mains voltage
Vin
3Ph+N 400 V -15% +20% (up to -40% @ 50% of nominal load)
Input frequency
Hz
50-60 ±10%
Input power factor
0.99
THDI
< 3%
Electrical specifications - External battery
Battery voltage range
V bat
from +/- 180
3
up to +/- 302
4
from +/- 190
3
up to +/- 302
4
Electrical specifications - Output
Output voltage
V
3Ph+N 380/400/415 V ±1%
1
Frequency
Hz
50-60 Hz ±0,2%
Automatic bypass
400 V ±15% (selectable from 10% to 20% if generator is used)
Nominal power
kW
90
108
Overload
(@ 25 °C; Vin >
380; Vbat > 240)
2
• 10 minutes
• 1 minute
kW
112,5
135
135
162
Crest factor
≥ 2.7
Voltage distortion
< 1% with linear load; < 4% with non-linear load
Environment
Operating temperature
°C
0÷35 (15÷25 recommended)
Storage temperature
°C
-5÷45
Relative humidity
%
up to 95%
Max. altitude
m
1000
Acoustic noise
dBA
< 65
Required cooling capacity
m
3
/h
2000
Dissipated power max
W
5299
7136
Dissipated power max
BTU/h
18,091
24,362
Standards
Safety
EN 62040-1/A1, EN 60950-1
Type and performance
EN 62040-3 (VFI-SS-111)
EMC
EN 62040-2 (Category C3)
Product certifi cation
CE - TÜV-SÜD
Protection level
IP20; IP21 on request
Mechanical characteristics with standard batteries
Dimensions (LxPxH)
mm
700 x 830 x 1925
Weight
kg
400