BATTERY CABINET ITYS PRO 10-20 kVA, MASTERYS 10-160 kVA- Ref.: IOMXXXABXX00-EN 01
4. ELECTRICAL INSTALLATION
NOTE!
Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
WARNING!
Before carrying out any operations, ensure that:
• The switch located inside the battery cabinet is open;
• The UPS is not live and all mains or battery switches are open;
• The switches upstream of the UPS are open.
Use the cables supplied with the unit to connect the UPS to the Battery cabinet.
Cabling errors with inversion of battery polarity may cause permanent damage to the equipment.
If using cabinets not supplied by the UPS manufacturer, it is the installer’s responsibility to check
electrical compatibility and the presence of appropriate protection devices between the UPS and
the battery cabinet (fuses and switches of sufficient capacity to protect the cables from the UPS
to the battery cabinet). As soon as the UPS is switched on (before closing the battery switches)
the battery parameters must be verified accordingly (voltage, capacity, number of elements, etc.)
on the mimic panel menu. If the values indicated on the battery cabinet data plate are different
from those shown on the mimic panel, please correct the settings.
IMPORTANT!
Protective earthing conductor (PE) must have sufficient current-carrying capacity. The PE cable
core size has to be chosen according to the PROTECTIVE CURRENT RATING of the earth circuit
which depends on the provision and location of overcurrent protective devices. We suggest
35mm² for Masterys Battery Cabinet.
Summary of Contents for ITYS PRO
Page 2: ......
Page 16: ......
Page 17: ...ITYPxxxxxxx2Pxx ITYS PRO 10 20kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 19: ......
Page 20: ......
Page 21: ...1MBFxxxxxxx4Pxx MASTERYS 10 40kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 24: ......
Page 25: ...2 x 1MBFxxxxxxx4Pxx MASTERYS 10 40kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 28: ......
Page 29: ...2 x 1MBFxxxxxxx2Fxx MASTERYS 10 40kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 32: ......
Page 33: ...2 x 1MBFxxxxxxx2Fxx MASTERYS 60 80kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 36: ......
Page 37: ...1MBFxxxxxxx4Fxx MASTERYS 10 80kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 40: ......
Page 41: ...2 x 1MBFxxxxxxx4Fxx MASTERYS 10 80kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 44: ......
Page 45: ...1MBFxxxxxxx2H 1 1MBFxxxxxxx20xx MASTERYS 10 80kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 51: ......
Page 52: ......
Page 53: ...1MBFxxxxxxx4Hxx MASTERYS 100 120kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 59: ......
Page 60: ......
Page 61: ...1MBFxxxxxxx2Hxx 1MBFxxxxxxx20xx MASTERYS 100 120kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 67: ......
Page 68: ......
Page 69: ...1MBFxxxxxxx4Mxx MASTERYS 160 kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 73: ......
Page 74: ......
Page 75: ...1MBFxxxxxxx2Mxx 1MBFxxxxxxx0Mxx MASTERYS 160 kVA 1 2 3 4 5 6 7 8 9 10 11 www socomec com...
Page 87: ......