Page 27 / 28
MEASUREMENTS: Address 0x
NN
60, 48 words
Code
Measurements
Units
ADDRESS
REMARKS
MO0
Load rate phase1
%
0x
NN
60
M01
Load rate phase 2
%
0x
NN
61
Set to 0xFFFF if one phase
M02
Load rate phase 3
%
0x
NN
62
Set to 0xFFFF if one phase
M03
UPS load rate
%
0x
NN
63
M04
Battery Capacity
%
0x
NN
64
M05
Battery Capacity
Ah*10
0x
NN
65
M06
Input bypass voltage phase 1
V
0x
NN
66
M07
Input bypass voltage phase 2
V
0x
NN
67
Set to 0xFFFF if one phase
M08
Input bypass voltage phase 3
V
0x
NN
68
Set to 0xFFFF if one phase
M09
Output voltage phase 1
V
0x
NN
69
M10
Output voltage phase 2
V
0x
NN
6A
Set to 0xFFFF if one phase
M11
Output voltage phase 3
V
0x
NN
6B
Set to 0xFFFF if one phase
M12
0x
NN
6C
Set to 0xFFFF (-1)
M13
0x
NN
6D
Set to 0xFFFF (-1)
M14
0x
NN
6E
Set to 0xFFFF (-1)
M15
Output current phase 1
A*10
0x
NN
6F
M16
Output current phase 2
A*10
0x
NN
70
Set to 0xFFFF if one phase
M17
Output current phase 3
A*10
0x
NN
71
Set to 0xFFFF if one phase
M18
Input bypass frequency
Hz*10
0x
NN
72
M19
Output frequency
Hz*10
0x
NN
73
M20
Battery voltage (+)
V*10
0x
NN
74
M21
Battery voltage (-)
V*10
0x
NN
75
Set to 0
M22
Ambient Temperature
°C
0x
NN
76
M23
Remaining backup time
Minutes
0x
NN
77
Set when the load is on battery
M24
Battery current
A*10
0x
NN
78
M25
0x
NN
79
Set to 0xFFFF (-1)
M26
0x
NN
7A
Set to 0xFFFF (-1)
M27
0x
NN
7B
Set to 0xFFFF (-1)
M28
Rectifier voltage (+)
V
0x
NN
7C
M29
Rectifier voltage (-)
V
0x
NN
7D
Set to 0
M30
V
0x
NN
7E
Set to 0xFFFF (-1)
M31
V
0x
NN
7F
Set to 0xFFFF (-1)
M32
0x
NN
80
Set to 0xFFFF (-1)
M33
Rectifier input voltage phase 1
V
0x
NN
81
M34
Rectifier input voltage phase 2
V
0x
NN
82
M35
Rectifier input voltage phase 3
V
0x
NN
83
M36
UPS output power
kW*10
0x
NN
84
M37
Output power phase 1
kVA*10
0x
NN
85
M38
Output power phase 2
kVA*10
0x
NN
86
Set to 0xFFFF if one phase
M39
Output power phase 3
kVA*10
0x
NN
87
Set to 0xFFFF if one phase
M40
0x
NN
88
Set to 0xFFFF (-1)
M41
0x
NN
89
Set to 0xFFFF (-1)
M42
0x
NN
8A
Set to 0xFFFF (-1)
M43
0x
NN
8B
M44
0x
NN
8C
M45
0x
NN
8D
M46
0x
NN
8E
M47
0x
NN
8F
Rectifier and battery measurements are not available in the ‘CC’ table (common bypass)