COUNTIS E41/E42 - 547979A - SOCOMEC
8.1.1. Detailed view of menu "SETUP 1"
In menu "SETUP 1" you can select the connection type.
Press SET for 3 seconds using a screwdriver to put the device into programming mode.
The default connection (Wir) is: 3.4.3 = 3 phases, 4 wires, 3 CT. Other possible connections: 3.3.3 = 3 phases, 3 wires, 3 CT
or 3.3.2 = 3 phases, 3 wires, 2 CT
SET
N
A
A-V
A
A-V
A
A-V
L1
L2
L3
L1
L2
L3
N
3 x 80A
230/400 VAC 50/60 Hz
1 2 3
4 5
6 7
NC - +
- +
COM RS485
MODBUS
T1/2
>3s
CT full scale value
x1
x1 Confirm
1 = CT secondary 1A
5 = CT secondary 5A
x1
CT ratio
x1
x1 Confirm
x1 or more to change the value
Repeat those 2 actions for the other digits
x1
Wiring diagram
x1
x1
3.4.3 = 3 phases, 4 wires, 3 CT
3.3.3 = 3 phases, 3 wires, 3 CT
3.3.2 = 3 phases, 3 wires, 2 CT
>3s
Exit setup
x1 Confirm
Y
=Save setting and exit
N
=Exit without saving
C
=Continue without saving