COUNTIS E13 / E14 - 545 869 A - SOCOMEC
6. CONNECTION
6.1. Connecting the COUNTIS E13/E14
L1
N
A
A-V
3 4 5
2
1
Fixed / flexible
0.14 mm
2
->
2.5 mm
2
0.27"
/ 6.9 mm
PZ2
4.5 lb.in
/
0.5 Nm max.
Fixed / flexible
1.5 mm
2
->
35 mm
2
0.47"
/ 12 mm
PZ2
17.70 lb.in
/
2 Nm max.
6.2. connection to the electrical network and to the loads
The COUNTIS E13/E14 are intended for single-phase networks with neutral.
Pulse output
1: +
2: -
Optocoupler pulse outputs
Terminals 1-2 must be supplied with voltage between 5
and 27 VDC (27mA max)
Modbus
3: NC (not connected). May be used for shielding
continuity.
4: -
5: +
Network
L1 A-V: Phase input
L': A: Phase output
N: Neutral connection
L1
N
A
A-V
L
L’
N
80A
230 VAC 50/60 Hz
3 4 5
2
1
NC
3 4 5
- +
COM RS485
MODBUS
-
+
2
1