6. CONNECTION
6.1. Connecting the COUNTIS E05/E06
L
L
N
N
4 5
2 3
Fixed / flexible
0.14 mm
2
->
2.5 mm
2
0.27"
/ 6.9 mm
PZ2
4.5 lb.in
/
0.5 Nm max.
Fixed / flexible
1.5 mm
2
->
6 mm
2
0.47"
/ 12 mm
PZ2
10.62 lb.in /
1.2 Nm max.
6.2. Connection to the electrical network and to the loads
The COUNTIS E05/E06 are intended for single-phase networks with neutral.
M-Bus
2-3: M-Bus connection
Pulse output
4: -
5: +
Optocoupler pulse outputs
Terminals 4-5 must be supplied with voltage between 5
and 27 VDC (27mA max)
Network
L: : Phase input
L': : Phase output
N: Neutral connection
L
L
N
N
4 5
L
L’
40A
N
230 VAC 50/60 Hz
2 3
COM
M-BUS
-+