NTROL / AUX POWER Terminals and wiring

  Set potentiometer for priority 

supply "Failure and Return Timer"

FT: 0-30 sec / RT: 0-30 min.

Ensure that the product is in Manual Mode 
(front cover open).

 

Source availability LED's

Type

Terminal 

no.

Description

Characte-

ristics

Recommanded 

connection  

cross-section

Inputs

207

Common

Do not 
connect to 
any power 
supply

0,5 to 2,5 mm²  
(rigid)

0,5 to 1,5mm² 
(stranded)

208

Position 0 order

209

Open SI priority.

Closed S2 
priority.

210

Inhibition ATS

Outputs

63/64

Open: SI and S2 
NOT available.

Closed: SI or S2 
available

73/74

Not used

Auxiliary 
contacts 
unit.

11/12/14 Position I

Dry 
potential 
 
250Vac 5A 
AC1
24Vdc 2A

21/22/24 Position II

01/02/04 Position 0

Source

LED ON

Source 1 
available

Source 2 
available

LED OFF

Source 1 not 
availlable

Source 2 not 
availlable

LED 
blinking

-  a timer is 

counting 
down

-  a timer is 

counting 
down

Slotted head 3mm 0,5 Nm

0,5  to  2,5 mm²

0,5  to  1,5 mm²

6 mm

207208 209 210 63 64 73 74

6

8

5

7

6

8

5

7

I1 I2 I3

O1

not used

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

1309 0001

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

1309 0011

Pozidriv PZ2 - 1 Nm

Use 20mm 

screws for 

1 module

U

s

1

se 20m

crews 

modu

U

sc

Use 35mm 

screws for 

2 modules

Auxiliary contacts: 

Fitting of auxiliary contacts: 

1309 0001 or 1309 0011

To fit an AC, the switch must first be put in position 0. An auxiliary contact module comprises: one 
NO/NC changeover contact for each position (I-0-II). To install use the long screws supplied with 
the module. 

STEP 1

  

The ATyS M is delivered with 
padlocking configured to the 
O position.

  

To allow padlocking in all 
positions (I - O - II), configure 
!""#!$
installation. (Screw is located 
at the back of the product).

STEP 3

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

Posidriv  PZ2 

2

Posidriv  PZ2 

Posidriv  PZ2 

Installation

Padlocking configuration

Caution: Ensure that the product is installed on a flat rigid surface.

53

46

73,5

45

340

326

131,5

131,5

52

104

176

47

Recommended orientation

Recommended

Ok

Ok

Ok

Ok

Ok

Posidriv  PZ1
1 Nm

 Tighten to avoid 

%&%*;<"=

DIN RAIL
IEC 60715

6 mounting brackets
6x M6 screw - 2,5 Nm

2x

2x

STEP 2

Power Terminal Connections

Source supply side

Hexagonal Metric
Allen size 4
5,0 Nm

  

It is essential to tighten 
""%<"!<"?@<J
!$<J?!@=

WG

m

2

m

2

*

WG

!

X

8

Y"J[![&<@\] =%%

2

 connections. 

They can be fitted in any terminals on the source 
supply side. Do not use on the load side when 
equipped with a bridging bar.

Load side 
bridging bar.
125A: 1309 4006
160A: 1309 4016

Slotted head  3,5 mm
0,45 Nm

0,5  to  2,5 mm²

0,5  to  1,5 mm²

6 mm

10 to 
70 mm²

15mm

MAX : 2

340

26

116

245

143

350

18

13

324

Step 1

Step 2

Step 3

Summary of Contents for ATyS t M

Page 1: ...EN INSTRUCTION MANUAL www socomec com ATyS t M Automatic Transfer Switching Equipment...

Page 2: ...com www socomec com en atys t m To download brochures catalogues and technical manuals This manual is available for download in French English German Italian Spanish Dutch Portugese Russian Polish Tur...

Page 3: ...ACCESSORIES 13 6 TECHNICAL DATA 14 15 8 PRODUCT INSTALLATION 16 8 1 CHANGING THE PADLOCKING CONFIGURATION 16 8 2 RECOMMANDED ORIENTATION 16 8 3 DIMENSIONS 16 8 4 BACK PLATE MOUNTED 16 8 5 DIN RAIL MO...

Page 4: ...RY CONTACT OPERATING SCHEDULE 25 13 OPERATION 26 13 1 PRESENTATION OF THE PRODUCT INTERFACE 26 13 1 1 PRODUCT INTERFACE 26 13 1 2 RESET 26 13 2 MANUAL MODE 27 13 2 1 MANUAL SWITCHING 27 13 3 PADLOCKIN...

Page 5: ...5 EN This page intentionally left blank...

Page 6: ...This instruction manual must be made accessible so as to be easily available to anyone who may need to read it in relation with the ATy The ATy 3 4 2 yS should be opened with or without voltage as th...

Page 7: ...J F J J G F G 9 3 8 J F G C8 D K 2 2 2 1 Just the right ATyS for your application ATyS Small Footprint 125A 3200A ATyS M Modular Profile 40A 160A 40A 125A 38 RTSE 8 2 Transformer L F38 G RTSE F G ATyS...

Page 8: ...BUILT IN ATS CONTROLLER COMMUNICATION TRIPPING Specific version Return to zero without external energy source Network Genset Genset Genset Network Network Applications with an External ATS Control Net...

Page 9: ...een keyboard Vn Fn V threshold F threshold Driving with or without priority Adjustable operating timers Control type impulse or switch contactor DISPLAY Position fully visualised breaking LED source s...

Page 10: ...Polycarbonate extension box Power Connection Terminals Sealable cover Printing informations 1 color Black White paper 90g m2 Printing size 420x297 Final size 210x297 This page visible first A separat...

Page 11: ...sc 1 Use 35mm screws for 2 modules Auxiliary contacts Fitting of auxiliary contacts 1309 0001 or 1309 0011 To fit an AC the switch must first be put in position 0 An auxiliary contact module comprise...

Page 12: ...andards and a 2 CAUTION Ensure that the load is connected to the top of the switch with the motorisation on the right hand side as shown 4 2 7 8 A fully integrated and interlocked transfer switch with...

Page 13: ...g and power supply tap voltage sensing can be mounted in the terminals without reducing their 3 Z Ref 2 parts ref Terminal shrouds 8 8 8 4 Z Ref 2 parts ref Enclosure K enclosure provides easy access...

Page 14: ...ts A 7 _ 2 2 2 B 2B 2 2 2 2 2 2 B 2B 2 2 2 2 2 2 B 2B 2 2 2 Rated operational F G 7 _ 2 2 2 B 2B 2 2 2 K circuit withstand if using 3 4 K circuit withstand kA eff F 3 4G B L kA eff L F G sensing time...

Page 15: ...15 EN 7 H B V _ V _ Temperature z _ _ _ F G Altitude UE B B B Storage z _ B V _ 1 mm 8 8 8 8...

Page 16: ...I and 0 refer to the following procedure 8 1 7 8 8 8 Posidriv PZ2 STEP 2 STEP 3 Posidriv PZ2 2 2 lb in 0 25 Nm STEP 1 Posidriv PZ2 2 Posidriv PZ2 2x 2x 8 2 Recommanded orientation Recommended Ok Ok Ok...

Page 17: ...17 EN 8 5 DIN rail mounted Posidriv PZ1 1 Nm Tighten to avoid DIN RAIL IEC 60715...

Page 18: ...mm 0 5 to 1 5 mm 6 mm 9 3 Bridging bars 4P L RJ RS 207208209210 43 44 53 54 63 64 73 74 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 RJ RS 207208209210 43 44 53 54 63 64 73 74 2 4 6...

Page 19: ...19 EN 9 4 Terminal shrouds L C K C K 9 5 Sealable cover L...

Page 20: ...ons and mounting F G L 9 F G I B Only 1 aux contact block may be installed when using this enclosure 193 mm 225 mm M6 275 mm M6 385 mm 385 mm 10 1 1 Wiring in a polycarbonate enclosure Example Neutral...

Page 21: ...ide Hexagonal Metric Allen size 4 5 0 Nm 10 to 70 mm 15mm It is essential to tighten all terminals even those that are not used 11 1 J K M B 9 recommended mm 9 recommended mm I 9 K Not compatible with...

Page 22: ...1 1 Auto transformer connections L Load I II 207 L32 L22 L12 L31 L21 L11 L1 1 3 5 7 2 N N 4 6 8 1 3 5 7 2 4 6 8 L2 L3 208 209 210 0 230 400 T2 400 230 V 400 VA 63 64 73 74 0 RM32 2P 1 A aM RM32 2P 1 A...

Page 23: ...head 3 5 mm 0 45 Nm 0 5 to 2 5 mm 0 5 to 1 5 mm 6 mm 5 A AC1 250 Vac 22 24 21 11 14 12 01 04 02 1309 0001 5 A AC1 250 Vac 22 24 21 11 14 12 01 04 02 1309 0011 All pressure on the connector pins is to...

Page 24: ...2 Not used I 2 B 9 F G 2 2 To restart the automatism you need to open the contact and to have an action to erase the fault manual mode G Type Terminal no Status of Description Output characteristics R...

Page 25: ...25 EN 12 2 Auxiliary contact operating schedule 11 14 Closed 11 12 Open 01 04 Closed 01 02 Open 21 24 Closed 21 22 Open 8 8 8 8 8 8...

Page 26: ...PERATION 13 1 V 13 1 1 V 3 2 availability indicators K M 3 M 3 8 3 1 1 2 5 3 4 1 Locking B 2 AUT MAN cover F G 3 Auto Manual mode sensor 4 Switch position indicators 3 5 Manual switching F G 13 1 2 Re...

Page 27: ...hangeover switch using Locking Manual changeover switching MANUAL MODE 13 2 1 Use the handle situated on the front panel under the cover K K K K Max 8 Nm Extension Do not force the product Max 8 Nm 13...

Page 28: ...counting down test mode Source 2 available Source 2 missing or out of range a timer is counting down Source availability LED E No stop in O position F 2s stop in O position Stop in 0 position E F Thre...

Page 29: ...29 EN 13 4 2 M 7 L 13 5 Automatic mode F 0 M 3 G 13 5 1 M J 2 2 13 6 Possible actions L 2 2 Source return source Loss of source source AUTOMATIC MODE...

Page 30: ...of the F G The use of any Megohmmeter is prohibited on this product as the connection terminals are intrinsically connected to the sensing circuit 15 TROUBLESHOOTING GUIDE 8 Actions 8 M 3 4 BB7 0 M 3...

Page 31: ...of 0 M 3 4 F G M 3 4 4 C 0L M 3 KKD F G The AUT and the backup 0L M 3 4 K F K G K I K 9 switch will operate to position The switch does not return to its priority position after the prio rity source...

Page 32: ...r Power Control Safety Tel 386 1 5807 860 Fax 386 1 561 11 73 info si socomec com SPAIN Critical Power Power Control Safety Tel 34 93 540 75 75 Fax 34 93 540 75 76 info es socomec com TURKEY Critical...

Reviews: