RTSE FASTON CONNECTIONS

VOLTAGE TRANSFORMER

480 VAC

240 VAC

PRIMARY

SECONDARY

NETWORK TYPE

TYPE 

SOURCE

A

B

C

N

H1

H4

X1

X4

240 VAC

2P

S2

S2A & 201

S2B 

None 

(1)

None 

(1)

S1

S1A & 102

S1B 

None 

(1)

None 

(1)

120/240 VAC

2P + N

S2

S2A & 201

S2B

None 

(1)

S2N

S1

S1A & 102

S1B

None 

(1)

S1N

208 VAC

3P

S2

S2A & 201

S2B

S2C 

None 

(1)

S1

S1A & 102

S1B

S1C 

None 

(1)

120/208 VAC

3P+N / 4P

S2

S2A & 201

S2B

S2C 

S2N 

S1

S1A & 102

S1B

S1C 

S1N 

277/480 VAC

3P+N / 4P

S2

S2A

S2B

S2C 

S2N & 201

S1

S1A

S1B

S1C 

S1N & 102

480 VAC + transfo

3P

S2

2xS2A

2xS2B

S2C 

-

T2A

T2B

T2A'

T2B'

S1

2xS1A

2xS1B

S1C 

-

T1A

T1B

T1A'

T1B'

(1) Cables which are not used are to be fastened as shown in image 4 of step 2B.

Connect the faston on the switch connexion according to your network and the table below:

Connection of harness on the switch

Controller connection details

2D

2C

TYPE

TERMINAL N° DESCRIPTION

CHARACTERISTICS

RECOMENDED

CROSS SECTION

TIGHTENING

TORQUE

Sensing source 1

SOURCE 1

L1/L2/L3/N

Voltage sensing inputs source 1

& voltage supply (L1-L2)

Sensing voltage

50 - 575 V.a.c P-P - 50/60 Hz (+/- 10%)

Supply voltage (L1-L2)

88 - 576 V.a.c - 50/60Hz (+/- 10%) Ui 600V

AWG 18-14

0.75-2.5mm²

0.5-0.6 Nm

4.4-5.3 lb.in

Sensing source 2

SOURCE 2

L1/L2/L3/N

Voltage sensing inputs source 2

& voltage supply (L1-L2)

Inputs

71

IN1: SWITCH IN POS1

Do not connect to any external power 

supply

AWG 20-14

0.5-2.5mm²

72

IN2: SWITCH IN POS 2

73

IN3: DOOR OPEN

74

IN4: programmable input 4

75

IN5: programmable input 5

76

IN6: programmable input 6

70

Common point for inputs

Aux power supply

81/82

- : negative terminal for aux supply

+: positive terminal of aux supply

12-24 Vd.c.

Outputs

12/14/11

OUT1: POS 1 ORDER

Dry contacts

8A / 277 VAC 50/60 Hz

5A / 24 VDC

AWG 16-14

1.5-2.5mm²

22/24/21

OUT2: POS 2 ORDER

32/34/31

OUT3: programmable output 3

42/44/41

OUT4: programmable output 4

52/54/51

OUT5: programmable output 5 (latching)

62/64/61

OUT6: genset start relay

Current transformers

IN/I3/I2/I1

CT neutal / CT phase C / CT phase B / CT phase A

CT input 1A or 5A

Serial connection

RS485

Connection RS485

-: negative terminal of RS485 bus

+: positive terminal of RS485 bus

NC : Ground

RS485 bus insulated

LiYCY shielded twisted pair

30-14 AWG / 0.14 to 1.5 mm²

1.9 - 2.2 Lb.in

0.22 -0.25 Nm

Digiware*

DIGIBUS

Connection point for I/O 10 optional accessories & 

digiware connection (must use 24 VDC input)

RJ 45 digiware cable

-

-

* For more information check I/O module instruction sheet ref 545597

Wiring harness connectors to place on controller.

Bottom view

Top view

Summary of Contents for ATyS FT

Page 1: ...s recommended to replace the complete product Installation standards must be respected Accessories Accessories are not included and must be ordered seperatly Terminal shrouds see step 6A Additional aux contacts ref 96990021 Digiware I O 10 ref 48290140 Transformer 480 240 VAC SPARTAN SP350MQMJ Controller 24 VDC aux power supply 6W minimum type SELV mandatory with I 0 10 Modules Power terminal lugs...

Page 2: ... 10 47 266 30 1 25 31 80 3 85 98 70 1 38 35 20 508 16 406 12 305 2P N 3P 11 85 301 30 1 25 31 80 5 49 133 70 1 38 35 20 508 16 406 12 305 3P N 4P 13 24 336 30 1 25 31 80 6 60 168 70 1 38 35 20 508 16 406 12 305 260 400A 2P 11 67 296 30 1 55 39 30 5 128 60 1 97 50 48 1220 24 610 12 305 2P N 3P 13 63 346 30 1 55 39 30 7 178 60 1 97 50 48 1220 24 610 12 305 3P N 4P 15 60 396 30 1 55 39 30 8 97 228 60...

Page 3: ...831 Contact us 1 6 250 KCMIL 275 31 1 5 16 70 8 8 5mm 1 25 4 100 200 A CMC LA 300R 39542020 2 1 6 300 KCMIL 275 31 1 5 16 70 8 8 5mm 1 12 28 4 39543020 3 39544020 4 260 400 A CMC LA 630R 39542040 2 1 4 600 KCMIL 550 62 1 1 2 310 35 8mm 1 79 45 7 39543040 3 39544040 4 260 400 A Ilsco D3096 Contact us 1 4 600 KCMIL 600 67 8 1 2 310 35 8mm 1 79 45 7 Power cable connections For 100A use 1 0 AWG For 20...

Page 4: ...ers not delivered with the product Fix FASTON connectors according to the table in step 2C Max 2 FASTON per pole Wires must not be in contact with active voltage points such as unused FASTON connections and lugs In order to do so any unused or loose cables must be tensed then fixed on a non conductive part of the transfer switch use cable tie fixation points as shown in the images below 1 Pass wir...

Page 5: ...4 4 5 3 lb in Sensing source 2 SOURCE 2 L1 L2 L3 N Voltage sensing inputs source 2 voltage supply L1 L2 Inputs 71 IN1 SWITCH IN POS1 Do not connect to any external power supply AWG 20 14 0 5 2 5mm 72 IN2 SWITCH IN POS 2 73 IN3 DOOR OPEN 74 IN4 programmable input 4 75 IN5 programmable input 5 76 IN6 programmable input 6 70 Common point for inputs Aux power supply 81 82 negative terminal for aux sup...

Page 6: ...n the configuration will go as follow SMART WIZARD CONFIG For advanced configuration go to parameters menu Language Source config Time date Switch Application Product Name Communication In STEP 5 8 of the wizard config make sure the network detected matches your network In STEP 6 8 make sure the switch technology parameter is set to ATyS FT If a fault is shown on the controller correct the associa...

Page 7: ...he LCD screen that may show distortion below 32 F 0 C Inspection of power contacts WARNING More than one live circuit Disconnect all sources of supply before servicing and or before using the manual operation Clip to maintain cover upright Slide cover to access service handle hole For manual operation operate handle 4 up from S2 to S1 down from S1 to S2 FAST OPERATION Recommendation carry out one ...

Page 8: ...and push back V Place the transparent plastic piece to cover the auxiliary conacts and lock in place in order to protect from direct contacts Use the correct protection according to your auxiliary contact circuit and your load Switch has 2 pre installed auxilliary contacts the kit below is for 2 additional contacts with protection against direct contact Ref 96990021 a b PH2 screwdriver Tightening ...

Reviews: