Chapter 4 : Central bypass systems
UPS/NTA GB/ DELMX_EXPC1C3C6.B
page 25
10.3.Mimic panel description
LEDS GREEN
YELLOW
RED
BLINKING
LED
1 RECTIFIER MAINS
OK Absent
2 RECTIFIER
ON Alarm
ON
3 BATTERY
Charged discharged
Green : discharging
4 INVERTER
ON Alarm
ON
5 MODULE CONNECTED
OK Eco-Mode
ON
6 OUTPUT TO THE COMMON
BUSBAR
supplied
Not supplied
Red : imminent stop
11 GENERAL ALARM
Alarm ON
10.4.Description of the luminous status bar on a module
Green bar
:
the module is connected to the common busbar.
Green blinking bar
: battery test in progress.
Yellow bar
:
the load is supplied via the battery (or the battery is discharged)
Yellow blinking bar
: alarm displayed or request for servicing.
Red bar
:
the module is not connected to the common busbar
Red blinking bar
:
the imminent shutdown alarm is given for the module.