SNIJDERS SCIENTIFIC
B.V.
ISO9001 certified by Lloyd’s
Economic Premium ECP01E, March ‘06
Page 20 of 22
Subject to change
8.
TROUBLESHOOTING
Machine completely ‘dead’
-
check main supply
-
check main fuse
-
check earthleakage-switch
Temperature too low
-
cooling valve open; active too long
-
thermal safety switch active
-
heating element defective
-
solid-state-relays heating defective
-
controller defective
Temperature too high
-
fan in cabinet broken
-
valve cooling-circuit defective
-
dirty condensor
-
compressor defective
-
compressor pressure too high/low
-
pressure-switch defective
-
ambient temperature too high
-
leakage refrigerant
Humidity too low
-
check if it’s possibly physical
-
check water level (main valve)
-
Stulz humidifier
-
check fan inside cabinet
Humidity too high
-
check temperature
-
check cooling system of defrost
-
check evaporator isn’t frozen
No lighting
-
relays defective
-
switching device, starter or light tubes
defective
-
thermal safety-switch active
-
check position control contacts