SMT FSC-UFC24 Technical Data Sheet Download Page 3

Technical Data Sheet FSC-UFC24

Page 3 of 18 

November 2017  

Technical changes reserved 

www.smtec-ag.ch

 

Installation

  The FSC-UFC24 is directly installed at or close to the fire or smoke 

extraction damper. The bracket can be pre-installed. The FSC-UFC24 can  

be snapped onto the bracket any time (at the damper manufacturer or  

at the job site).

 

 

Electrical Installation

  See details page 7.

 

Safety Notes

  The FSC-UFC24 is not allowed to be used outside the specified field 

of application, especially in aircraft or in any other airborne means of 

transport. 

 

  The company buying and / or mounting the FSC-UFC24 on site bears 

full responsibility for the proper functioning of the whole system. Only 

authorized specialists may carry out the installation. All applicable legal 

or institutional installation regulations must be complied with during 

installation.

 

  The device contains electrical and electronic components and is not 

allowed to be disposed of as domestic refuse. All locally valid regulations 

and requirements must be observed.

  Product Features / Application

  The FSC-UFC24 is used together with a fire or smoke extraction damper 

actuator to control and monitor one fire or smoke extraction damper. It 

offers Modbus, BACnet or analog connection and is normally mounted at 

or close to the damper. Following control modes can be chosen through 

dip switch terminal:

 

  •  Fire or smoke extraction application

 

  •  Bus protocols: Modbus or BACnet

 

  

 

  Conventional: Analog output and digital input signals for conventional 

application.

 

 

  This digital input in the FSC-UFC24 always overrides the bus commands.

 

  

 

  Universal System Link between fire or smoke extraction damper and any 

Modbus or BACnet system or analog control.

  

 

Power Supply

  The FSC-UFC24 needs to be powered up with 24 V AC / DC. The 

FSC-UFC24 provides the power supply to the actuator and to other 

connected devices (e. g. smoke detector). For more details see page 7.

Summary of Contents for FSC-UFC24

Page 1: ...r Baud Rates 9 600 19 200 38 400 76 800 bps Address 1 127 1 10 reserved for FSC M200 0 reserved for broadcast Termination 120 line termination Jumper available on extra pin on PCB Position of jumper i...

Page 2: ...ime 100 ms Device Instant Automatically assigned by physical address writable Safety Protection Class III safety extra low voltage Protection Degree IP42 housing of non flammable polycarbonate Electro...

Page 3: ...he device contains electrical and electronic components and is not allowed to be disposed of as domestic refuse All locally valid regulations and requirements must be observed Product Features Applica...

Page 4: ...hrough a digital output signal There is one analog output to signalize the status of the FSC UFC24 and the actuator This analog output can be read from any controller Communication Serial Communicatio...

Page 5: ...ata Sheet FSC UFC24 Page 5 of 18 November 2017 Technical changes reserved www smtec ag ch 153 mm 57 mm incl bracket 120 mm 116 mm 70 mm 153 mm 130 mm 4 5 mm diameter 100 mm FSC UFC24 Mounting Bracket...

Page 6: ...cover 2 Unlock the screw which is placed on the lower end in the middle 3 Move the sliding cover 10 mm to the top 4 Remove the cover Lid for Easy Access to Dip Switch Terminals Configuration Addressi...

Page 7: ...ly Open Position of line termination 120 if FSC UFC24 is last Modbus or BACnet device in line Smoke Detector 24VDC Power supply max 25mA Digital input 24V Can be selected via bus as Normally Open or N...

Page 8: ...73 1 4 7 106 2 4 6 7 8 4 41 1 4 6 74 2 4 7 107 1 2 4 6 7 9 1 4 42 2 4 6 75 1 2 4 7 108 3 4 6 7 10 2 4 43 1 2 4 6 76 3 4 7 109 1 3 4 6 7 11 1 2 4 44 3 4 6 77 1 3 4 7 110 2 3 4 6 7 12 3 4 45 1 3 4 6 78...

Page 9: ...of the smoke detector is transferred directly to the system and processed there Smoke Detector Alarm Actuator The signal of the smoke detector is directly linked with the actuator In case of a smoke d...

Page 10: ...p the power to the actuator is on output open pin nr 1 On power up the CLOSE output will be ON During normal operation the FSC UFC24 in this application ONLY will hold the last command on memory 3 2 1...

Page 11: ...l AMP plug 2 pole Quick connector 3 pole When a thermoelectric tripping device is mounted in the 2 pole AMP plug the factory production mounted jumper between DI3 and C must be removed The above is on...

Page 12: ...ct The ORS 142 may only be connected to Hekatron mainspower devices and matches the existing bases type 143 FSC UFC24 24V DC X X X X 6 3 6 5 6 3 6 5 6 3 6 5 24V DC DI2 Com External power supply ABAV S...

Page 13: ...ipping Device Alarm 10V More than one Alarm Condition During normal operation this output will signalize the position of the damper 2V 4V This output can be connected in parallel between the various F...

Page 14: ...ontroller with analog input Analog Input Smoke Detector AO 1 Com Analog Ouput Signals the Status of FSC UFC24 0V No Power to FSC UFC24 2V Damper Open 4V Damper Close 6V Smoke Detector Alarm 8V Thermoe...

Page 15: ...on On Analog connection Error Red Flash Interval 1 sec Actuator did not reach end switch position within the set time Flash Interval 2 sec Smoke detector alarm Flash Interval 3 sec Thermoelectric trip...

Page 16: ...g test button will interrupt the power supply to the actuator Spring is closing the actuator As soon as the test button is released the power comes back to the actuator and the damper will open again...

Page 17: ...itch has been reached The timer of the run time monitoring starts to count again as soon as the command open has been sent Once the timer of the set running time has reached the set time the FSC UFC24...

Page 18: ...1 on Logic Alarm Delay is activated default delay time is 120 sec Option to set the delay time via bus between 30 360 sec Functionality Fire Damper After the defined period of time the fire damper wil...