SMT FSC-UFC24 Technical Data Sheet Download Page 17

Technical Data Sheet FSC-UFC24

Page 17 of 18 

November 2017  

Technical changes reserved 

www.smtec-ag.ch

The FSC-UFC24 is equipped with an actuator run time monitoring function. This function monitors the time 

required by the actuator from leaving of the one and reaching of the other end switch. If the actuator does 

not reach the other end switch in the specified time an error message is sent.

The default value for the actuator run time is 90 seconds. This can be adapted via Modbus or BACnet from 

0…360 seconds.

The FSC-UFC24 offers a ‘Full Auto Test’ function. This can be controlled through the Modbus or BACnet 

controller.

Basis of the Functionality

Basis for this function is the run time monitoring of the actuator.

Fire Damper

To start the full auto test functionality, the corresponding bus-register hast to be activated via bus. By starting 

the full auto test, the timer of the run time monitoring starts to count the time and the fire damper actuator is 

closing (spring) and remains in the closed position until the timer of the set running time has reached the set 

time. Then the actuator will open again automatically until the end switch has been reached. The timer of the 

run time monitoring starts to count again as soon as the command ‘open’ has been sent. Once the timer of 

the set running time has reached the set time, the FSC-UFC24 will go back into normal operation mode and a 

feedback ”full auto test ok” is activated. If one of the end switches is not reached within the defined running 

time, an error message is activated. 

Smoke Extraction Damper 

To start the full auto test functionality, the corresponding bus-register has to be activated via bus. By starting 

the full auto test, the timer of the run time monitoring starts to count the time and the smoke extraction 

damper actuator is moving to the opposite direction and remains in that position until the timer of the 

set running time has reached the set time. Then the actuator will automatically move back to the original 

position until the end switch has been reached. The timer of the run time monitoring starts to count again as 

soon as the command ‘opposite direction’ has been sent. Once the timer of the set running time has reached 

the set time, the FSC-UFC24 will go back into normal operation mode and a feedback ”full auto test ok” is 

activated. If one of the end switches is not reached within the defined running time, an error message is 

activated.

Run Time Monitoring of Actuator

Full Auto Test Application

Summary of Contents for FSC-UFC24

Page 1: ...r Baud Rates 9 600 19 200 38 400 76 800 bps Address 1 127 1 10 reserved for FSC M200 0 reserved for broadcast Termination 120 line termination Jumper available on extra pin on PCB Position of jumper i...

Page 2: ...ime 100 ms Device Instant Automatically assigned by physical address writable Safety Protection Class III safety extra low voltage Protection Degree IP42 housing of non flammable polycarbonate Electro...

Page 3: ...he device contains electrical and electronic components and is not allowed to be disposed of as domestic refuse All locally valid regulations and requirements must be observed Product Features Applica...

Page 4: ...hrough a digital output signal There is one analog output to signalize the status of the FSC UFC24 and the actuator This analog output can be read from any controller Communication Serial Communicatio...

Page 5: ...ata Sheet FSC UFC24 Page 5 of 18 November 2017 Technical changes reserved www smtec ag ch 153 mm 57 mm incl bracket 120 mm 116 mm 70 mm 153 mm 130 mm 4 5 mm diameter 100 mm FSC UFC24 Mounting Bracket...

Page 6: ...cover 2 Unlock the screw which is placed on the lower end in the middle 3 Move the sliding cover 10 mm to the top 4 Remove the cover Lid for Easy Access to Dip Switch Terminals Configuration Addressi...

Page 7: ...ly Open Position of line termination 120 if FSC UFC24 is last Modbus or BACnet device in line Smoke Detector 24VDC Power supply max 25mA Digital input 24V Can be selected via bus as Normally Open or N...

Page 8: ...73 1 4 7 106 2 4 6 7 8 4 41 1 4 6 74 2 4 7 107 1 2 4 6 7 9 1 4 42 2 4 6 75 1 2 4 7 108 3 4 6 7 10 2 4 43 1 2 4 6 76 3 4 7 109 1 3 4 6 7 11 1 2 4 44 3 4 6 77 1 3 4 7 110 2 3 4 6 7 12 3 4 45 1 3 4 6 78...

Page 9: ...of the smoke detector is transferred directly to the system and processed there Smoke Detector Alarm Actuator The signal of the smoke detector is directly linked with the actuator In case of a smoke d...

Page 10: ...p the power to the actuator is on output open pin nr 1 On power up the CLOSE output will be ON During normal operation the FSC UFC24 in this application ONLY will hold the last command on memory 3 2 1...

Page 11: ...l AMP plug 2 pole Quick connector 3 pole When a thermoelectric tripping device is mounted in the 2 pole AMP plug the factory production mounted jumper between DI3 and C must be removed The above is on...

Page 12: ...ct The ORS 142 may only be connected to Hekatron mainspower devices and matches the existing bases type 143 FSC UFC24 24V DC X X X X 6 3 6 5 6 3 6 5 6 3 6 5 24V DC DI2 Com External power supply ABAV S...

Page 13: ...ipping Device Alarm 10V More than one Alarm Condition During normal operation this output will signalize the position of the damper 2V 4V This output can be connected in parallel between the various F...

Page 14: ...ontroller with analog input Analog Input Smoke Detector AO 1 Com Analog Ouput Signals the Status of FSC UFC24 0V No Power to FSC UFC24 2V Damper Open 4V Damper Close 6V Smoke Detector Alarm 8V Thermoe...

Page 15: ...on On Analog connection Error Red Flash Interval 1 sec Actuator did not reach end switch position within the set time Flash Interval 2 sec Smoke detector alarm Flash Interval 3 sec Thermoelectric trip...

Page 16: ...g test button will interrupt the power supply to the actuator Spring is closing the actuator As soon as the test button is released the power comes back to the actuator and the damper will open again...

Page 17: ...itch has been reached The timer of the run time monitoring starts to count again as soon as the command open has been sent Once the timer of the set running time has reached the set time the FSC UFC24...

Page 18: ...1 on Logic Alarm Delay is activated default delay time is 120 sec Option to set the delay time via bus between 30 360 sec Functionality Fire Damper After the defined period of time the fire damper wil...