PROTECTION 

 

The unit is protected in the event of fan failure, or an obstruction of the free 

airflow, by a single thermal PTC Self Hold Cut-out.  Having tripped, the PTC 
Cut-out remains open, effectively switching off the heating elements as long 
as mains power is available inside the appliance.  The PTC Cut-out will only 

reset when the appliance is switched OFF and allowed to cool for at least 20 
minutes. 
 

MOUNTING 

The  normal  mounting  height  is  2.3m  above  the  floor,  although  this  will 
depend  to  some  extent  on  the  situation.    The  unit  should  be  mounted  at 

least  200mm  below  ceiling.  The  heater  can  be  arranged  to  blow  air  at  any 
angle,  from  horizontal  to  vertically  downwards,  subject  to  the  conditions 
mentioned  below.    It  is  suggested  that  an  angle  of  45  deg  is  a  convenient 

starting point when setting up the unit. It must always be installed with the 
axis  of  the  motor  horizontal.  Failure  to  ensure  this  will  result  in  excessive 
bearing wear and premature failure. 
A mounting bracket is provided for mounting to a wall. 

 

The heater should not be mounted in situations where it may be subject to 
conditions of excessive humidity or the atmosphere is corrosive. 

 

INSTALLATION 

IN  ALL  CASES,  THE  UNIT  SHOULD  BE  WIRED  IN  ACCORDANCE  WITH  IET 

REGULATIONS FOR THE ELECTRICAL EQUIPMENT OF BUILDINGS. 

 
Loosen mounting screws, allowing the mounting bracket to be removed from 

the unit.  Making sure that the mounting bracket is horizontal, fix the bracket 
to the wall using 3 x No 8 wood screws. 
 

Place the unit on the mounting bracket ensuring the washers are spaced as 
on diagram. 
 
Tighten screws to hold the unit at the required angle. 

 

 
 
 
 
 
 
 
 
 
ELECTRICAL CONNECTIONS 

This unit is suitable for connection to a 230/240V 50Hz single phase AC 
supply. The unit consumes 3kW of electrical power when the fan and heater 
are in operation. Connection to the mains supply should be via a switched 

fused isolator.

 

 
To  connect  a  supply  to  the  heater  the  curved  top  cover  first  needs  to  be 

removed. Looking directly at the output grille the top cover is secured by two 
screws which are located at the upper left and right of the outlet grille. Once 
the 2 screws are removed the curved top cover can be removed by lifting it 

up and away from the output grille, then lifting off the cover from the two 
slot hinges located at the opposite side to the two screws/output grille. The 
input terminal block, marked ENL, is fitted at the left-hand side of the unit 

looking from above (at the opposite end to the fan motor). 
To the unit connect a suitable length of 3 core 1.5 mm

flexible cable to the 

input terminal block marked ENL.   

 
For safety reasons, a sound earth connection MUST ALWAYS be made to the 
unit before being used. 
 

Controller 

The unit is supplied with a SLVT-B wireless controller. This controller must be 
used in conjunction with the heater.  

Important: The heater will not function without the controller. 
 

The  controller  should  be  positioned  1.5m  above  the  floor  and  in  the  same 

room as the heater. The controller should be fixed to the wall. Avoid areas 
with draft or direct sun. Do not position the controller above or close to the 
heater or other heat sources. Damp areas or areas where the controller can 

be  mechanically  damaged  should  also  be  avoided.  Avoid  installing  the 
controller  in  areas  where  there  are  metal  objects  between  the  heater  and 
the controller. This will reduce the RF range. The RF range in ideal conditions 

can  be  up  to  20m  however  this  can  be  reduced  when  the  signal  is  passing 
through the walls or other objects. The range can be also affected where the 
controller is mounted close to power cables, motors or equipment producing 
strong electromagnetic field. If the temperature control feature is used it is 

necessary to use one controller for each room or zone. 
 

TO RESET THE PTC SELF HOLD CUT-OUT 

DO NOT ADJUST BY HAND ANY INTERNAL COMPONENTS 
 

a)

 

The cut-out is reset by switching OFF mains power to the appliance. 

b)

 

Allow the appliance to cool for 20 minutes 

c)

 

Reconnect mains power, switch ON the appliance. 

d)

 

If the cut-out trips again the appliance and installation should be 

checked by a qualified electrician. 
 

TO REPLACE A SWITCH 

a)

 

Ensure mains supply is switched off. 

b)

 

Remove the top cover. 

c)

 

Remove the push-on connectors, noting their position. 

d)

 

Remove copper links, noting their position. 

e)

 

Remove switch by compressing the plastic retaining tabs and lifting out 

the switch. 

f)

 

Insert the new switch, refit copper links and push on connectors in the 
correct order. 

g)

 

Test and reassemble. 

 

TO REPLACE THE FAN HEATER ASSEMBLY 

a)

 

Ensure mains supply is switched off. 

b)

 

Remove the top cover. 

c)

 

Disconnect the internal wiring from the main terminal block. 

d)

 

Remove the four nuts and washers fixing the fan heater assembly and 
earth tag to the back of the case. 

e)

 

The fan heater assembly can now be eased forward and removed from 
the heater case. 

f)

 

Fit replacement fan heater and reassemble in reverse order. 

 

IF YOUR HEATER DOES NOT WORK 

 

 

Check that the unit is wired correctly 

 

Check that the fuse has not blown in the connection to the unit 

 

Check re-set of PTC (as described under relevant section) 

 

Check the SLVT-B controller is calling for heat. 

 

Check the unit is paired with the SLVT-B controller 

 

Check the battery condition in the SLVT-B controller and replace if 
necessary 

 

Do NOT attempt to repair the heater yourself 

Should none of the above remedies work, disconnect heater from power 
supply and consult accredited service agent. If the appliance is still under 
guarantee, return it to your supplier. 