FAULT FINDING
Fan does not run on any switch setting
•
Check the power source is switched ON
•
Check fuse in the fused spur
•
Check wiring connections at the fused spur
No heat output on settings I and II
•
Check the power supply is switched ON
•
Ensure the room thermostat is calling for heat
•
Check the heat source switch is in the correct mode
•
Balance the central heating system if installed on the same circuit as panel
radiators and increase the circulating pump speed if required.
•
Increase the heat source water temperature
In the event of difficulty please contact us on 01245 324560. It will be more helpful if
you do not remove the product from the central heating system.
We would be most grateful if you would leave this installation & operation guide and
the guarantee registration card with the owner of the property.
USER GUIDE
Your product is covered by a free 5-year parts and labour guarantee; please
complete and return the Guarantee Registration Card to us as soon as possible to
ensure that should you require assistance, we can help you quickly and efficiently.
Your Ecovector™ is designed to operate as part of your central heating system in the
same way as a panel radiator. Providing you leave the heater switches in their
normal operating positions it will switch on and off automatically with you central
heating system.
Heat from your central heating system passes through a heat exchanger transferring
its heat to the aluminium fins, room air is drawn in the top grille and heated as it
passes through the heat exchanger before being gently expelled back into the room
at floor level.
6
Fix the EZ hanger to the wall, position the heater on the EZ hanger and secure to the
wall at the five fixing points.
PIPE WORK
We recommend the use of full flow isolating valves. These valves should be
accessible after completion of the installation. Pipe work can be brought out from the
heater directly or through the rear chassis. A lower panel blanking plate is packed
and supplied with the heater if the latter option is used (to fit this remove the 3 screws
from the fitted slotted pipe access panel and replace with the blanking plate).
Connect the heating system flow and return pipes to the heater pipe work. Do not
use soldered fittings to the heater pipe work as he heat generated could damage
internal wiring and components. The pipe nearest the front of the heater is the supply
flow and the pipe nearest the chassis is the return.
Check for water leaks. Remove any trapped air from the system via the vent valve
on the top left hand side of the heat exchanger. Do not over tighten the air vent
3