background image

6

Where required by the local authorities having jurisdiction, a fuel 

cleaning device such as a filter or strainer should be installed in 

the main gas supply line to the unit (see Figure 1 on Page 3).
A  gas  service  pressure  regulator  is  required  to  maintain  the 

gas  supply  pressure  below  the  maximum  allowable  pressure 

indicated  on  the  appliance  rating  plate. A  gas  pressure  relief 

valve, if required by the local code authority, should be installed 

upstream of all operating and safety controls in the gas train 

and downstream of the gas pressure regulator in the gas supply 

line (see Figure 1 on Page 3).
Pertinent operating, cleaning and testing procedures are outlined 

in this supplement in the TESTING AND MAINTENANCE section.
A Manufacturer’s/Installing Contractor’s Report for ASME CSD - 

1 Certification and Reporting (CG-500) requirements is provided 

with  the  instructions.  This  report  shall  be  made  available  to 

the  authorized  inspection  agency  or  the  inspector  for  action 

as required by the local jurisdiction. Installing contractors shall 

maintain a data report for each installation completed. It is the 

responsibility of the installing contractor to deliver the pertinent 

operating,  cleaning  and  testing  procedures  together  with  the 

complete wiring and piping diagrams, to the owner/user and to 

obtain a receipt for the instructions. The receipt shall be filed with 

the installation report.

TESTING AND MAINTENANCE

Periodic  testing  of  all  boiler  controls  and  safety  devices  is 

required to verify correct operation. Precautions shall be taken 

to protect against bodily injury or property damage while tests 

are  being  conducted.  Cover  plates  that  require  removal  in 

order to gain access to items requiring maintenance or testing 

shall be replaced before the boiler is put back in service. Since 

it  is  essential  to  have  all  control  and  safety  devices  operating 

as  intended  at  all  times,  a  periodic  testing  and  maintenance 

schedule should be set up and followed with results being logged 

on a regular basis. Operators or maintenance technicians should 

follow the recommended procedures set forth in the instructions 

and allow for any additional circumstances that arise based on the 

particular  installation  when  preparing  a  maintenance  program. 

The  operator  or  technician  should  thoroughly  understand  the 

operating  procedures  and  be  able  to  recognize  an  equipment 

malfunction.  Obtain  a  receipt  for  the  instructions.  The  receipt 

shall be filed with the installation report.
Table 1, provided herein is a recommended guideline to follow 

for  periodic  testing  of  the  boiler's  safety  devices  and  controls. 

Detailed maintenance procedures are included here as well.

ITEMS

FREQUENCY

ACCOMPLISHED BY

REMARKS

1. Gauges and Indicators

Daily

Operator

Visually inspect, log observations.

2. Burner Flame

Daily

Operator

Visually inspect for uniform blue flames.

3. Pilot Burner

Daily

Operator

Visually inspect for uniform flame envelope.

4. Flame Failure Detection

Weekly

Operator

Close Pilot Manual Shutoff Valve, check 

safety shutdown time, log results.

5. Gas Valves

Weekly

Operator

Open Operating Control, listen for valve 

closure, check for voltage.

6. Flow Switch

Weekly

Operator

See detailed instructions.

7. Vent System

Monthly

Operator

See detailed instructions.

8. Optional Power Vent

Monthly

Operator

See detailed instructions.

9. Burner Components

Monthly

Service Technician

See Owner’s Manual

10. Heat Exchanger Assembly

Semi-Annually

Service Technician

See detailed instructions.

11. Transformer

Semi-Annually

Service Technician

Check primary and secondary voltage, log 

results.

12. Manual Reset High Limit and 

Auto Reset High Limit

Annually

Service Technician

See detailed instructions.

13. Safety Valves

As Required

Operator

See detailed instructions.

14. Drip Leg and Gas Strainer

As Required

Operator

See detailed instructions.

TABLE 1.  PERIODIC TESTING PROCEDURES

TESTING AND MAINTENANCE

Summary of Contents for HW 420

Page 1: ...rity having jurisdiction requires that the installation must conform to the standard for Controls and Safety Devices for Automatically Fired Boilers ASME CSD 1 The rules of the code cover the requirem...

Page 2: ...TROL DIAGRAM 3 WIRING DIAGRAM 4 OPERATING SEQUENCE 5 OPERATING SEQUENCE WHEN WIRED AS SHOWN 5 TESTING AND MAINTENANCE 6 INSTRUCTIONS FOR TESTING AND MAINTENANCE 7 DAILY CHECKS 7 WEEKLY CHECKS 7 MONTHL...

Page 3: ...information on this Hot Water Boiler installation see Instruction Manual 321078 000 The wiring changes brought about by the addition of the Figure 2 manual reset High Limit and the Flow Switch are ref...

Page 4: ...4 Figure 3 WIRING DIAGRAM WIRING DIAGRAM...

Page 5: ...the pump providing sufficient water flow the flow switch will close contacts allowing power to be supplied to the transformer through the manual reset high limit 4 Power continues through the normally...

Page 6: ...nd safety devices operating as intended at all times a periodic testing and maintenance schedule should be set up and followed with results being logged on a regular basis Operators or maintenance tec...

Page 7: ...bly inspected on a daily basis for normal operation These items should be noted and the differential temperatures recorded during operation If the temperature differential increases by five 5 degrees...

Page 8: ...8 25589 Highway 1 McBee SC 29101 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: