ProtoNode Start-Up Guide
Page 8 of 37
3.4
Configure the DIP Switches
3.4.1 Setting the Node/ID Device Instance (DIP Switch A0
– A7)
The A Bank DIP switches on the ProtoNode allow users to set the Node-ID/Device Instance on
the Field RS-485.
DIP switches A0
– A7 can also be used to set the MAC Address for BACnet MS/TP and
BACnet/IP.
A0
A1
A2
A3
A4
A5
A6
A7
Off
On
NOTE:
When setting DIP Switches, please ensure that power to the board is OFF.
Refer to
Appendix B.1
for the full range of addresses to set Node-ID/Device Instance.
3.4.2 Setting the Serial Baud Rate (DIP Switch B0
– B3)
DIP Switches B0
– B3 can be used to set the serial baud rate to match the baud rate provided by
the interfaced systems.
Metasys N2 is always defaulted to 9600 baud and the B bank is disabled.
“B” bank DIP switches B0 – B3 are disabled on ProtoNode FPC-N35 (LonWorks).
B0
B1
B2
B3
Off
On
Figure 1: A0 - A7 DIP Switches
Figure 2: B0
– B3 DIP Switches