ProtoNode Start-Up Guide
Page 20 of 37
6
LONWORKS (FPC-N35): COMMISSIONING PROTONODE ON A LONWORKS
NETWORK
Commissioning may only be performed by the LonWorks administrator.
6.1 Commissioning ProtoNode FPC-N35 on a LonW orks Network
The User will be prompted by the LonWorks Administrator to hit the Service Pin on the ProtoNode
FPC-N35 at the correct step of the Commissioning process which is different for each LonWorks
Network Management Tool.
If an XIF file is required, see steps in
Section
6.1.1
to generate XIF.
6.1.1 Instructions to Download XIF File from ProtoNode FPC -N35 Using Browser
Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and
ProtoNode.
The Default IP Address of ProtoNode is
192.168.1.24
, Subnet Mask is
255.255.255.0
. If the PC
and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the
192.168.1.xxx network.
For Windows XP:
Go to
>
>
Right-click on Local Area Connection > Properties
Highlight
>
For Windows 7 or later:
Go to
>
>
>
>
Right-click on Local Area Connection > Properties
Highlight
>
Figure 18: LonWorks Service Pin Location