HARDWARE CONNECTIONS
The FieldServer is connected to the DeviceNet network as shown in the connection drawing below.
DeviceNet Status LEDs
1
2
3
4
5
FieldServer
DeviceNet Connection Points
V-
V+
To DeviceNet Network
1
2
3
4
5
Pluggable screw 5.08 & 3.84 mm
Connector Pinouts
Pin
Signal
Description
Wire color
1
V-
Negative supply voltage black
2
CAN_L
CAN_L Bus line
blue
3
SHIELD Cable Shield
(bare)
4
CAN_H CAN_H Bus line
white
5
V+
Positive Supply Voltage red
3.1
Hardware Connection Tips / Hints
•
Use the recommended network cable and terminators as specified by the DeviceNet network
organization and/or the manufacturer of your network equipment.
•
Terminate each end of the DeviceNet network with a 121 Ω resistor.
•
The bus interface shall be supplied with 24DC ± 10% on the Fieldbus connector.
•
The DeviceNet Slave Card's network current consumption is maximum 30mA = 0.03 Amps.