DEVICENET SLAVE DESCRIPTION
The DeviceNet Slave Adapter driver can be used to emulate a single slave station on a DeviceNet
network. The FieldServer DeviceNet adapter is implemented as an ODVA profile 12 communications
adapter and acts as a group 2 only server on the DeviceNet network. Standard DeviceNet baud rates of
125k, 250k and 500kbit/s are supported. DeviceNet masters/scanners can open an IO connection of up to
512 Bytes in each direction to the FieldServer.
Max Nodes Supported
FieldServer Mode Nodes Comments
Server
1
The FieldServer can only emulate one DeviceNet Slave station
2
DRIVER SCOPE OF SUPPLY
2.1
Supplied by Sierra Monitor Corporation
PART #
Description
DeviceNet-Slave Anybus-S DeviceNet Card
2.2
Provided by the Supplier of 3
r d
Party Equipment
2.2.1 Required 3
r d
Part y Software
RSNetWorx, RSLogix or another Network Scheduling Tool.
2.2.2 Required 3
r d
Part y Configuration
Connection to a properly terminated DeviceNet network.
2.2.3 Optional Item s
PART # Vendor/Manufacturer Description
-
HMS-Networks
Anybus-S DeviceNet EDS file