Stulz Driver Manual
Page 5 of 16
HARDWARE CONNECTIONS
The FieldServer is connected to the Stulz device over RS-485 as shown in the connection drawings below.
NOTE: Configure the Stulz C6000 according to the
manufacturer’s instructions.
C6000
Device 1
C6000
Device 2
C6000 Device
32
...
FieldServer to C6000
Connection Diagram
FieldServer
Orange/
White
–
4
C
O
M
+
–
GND
Blue/White
+
Brown
2.1
Hardware Connection Tips / Hints
•
Connect the wire to bus 1 on the Stulz device. Make sure that bus 1 is used as bus 2 is used by
the device to communicate with its IO devices.
•
Use shielded twisted pair wire to make connections.
•
Use terminating resistors. The Stulz device has terminating resistors which are set with a jumper.
•
Make sure that line is terminated at both ends to ensure maximum communication efficiency.
•
For C6000 controller information, email Stulz at
14
13
12
11
10
9
8
7
6
5
4
3
2
1
BUS1H
BUS1L
RS485
+
RS485
-
Detail of Pin Arrangement
Showing Connections