[F 1] Setting of OUT1
Set the output mode of OUT1.
Output turns on when the pressure is greater than the set value. The default setting is to turn on the product
when the pressure reaches the center of the atmospheric pressure and upper limit of the rated pressure range.
Output ON lights in green and output OFF lights in red as default setting.
Please refer to the "List of output modes" on page
for the relationship between the set items and operation.
<Operation>
Press the UP or DOWN button in function selection mode to display [F 1].
Press the SET button.
Move on to output mode setting.
Output mode setting
Press the UP or DOWN button to select the required output mode.
Press the SET button to set.
Move on to reversed output setting.
Reversed output setting
Press the UP or DOWN button to select the
reversed output.
Press the SET button to set.
Move on to pressure setting.
Pressure setting
Set the pressure based on
the setting method on
page
Hysteresis mode: [P_1]
Window comparator mode: [P1L] [P1H]
"P" is changed to "n" as [P_1]
[n_1] when
reversed output is selected.
The snap shot function can be used.
(Refer to page
Press the SET button to set.
Move on to hysteresis setting.
[OFF] Switch output
OFF is selected.
Press the SET button
to move on to display
colour setting.
[Err] Error output is
selected.
Press the SET button to
move on to display
colour setting.