[F 6] Fine adjustment of display value
This function is to manually perform a fine adjustment of the displayed pressure value.
Pressure can be adjusted in the following range of
5%R.D.
<Operation>
Press the UP or DOWN button in function selection mode to display [F 6].
Press the SET button.
Move on to fine adjustment of display value.
Fine adjustment of display value
Press the UP or DOWN button to change adjustment rate.
When adjustment rate is changed, the pressure value after the
adjustment will be displayed on the main screen.
Press the SET button to set.
Return to function selection mode.
[F 6] Fine adjustment of display value completed