-51-
No.PF
※※
-OMU0007-B
■
[F30] Accumulated value hold setting
This function enables the accumulated flow value to be stored in permanent memory every 2 or 5 minutes.
In the default setting, the accumulated flow value is not held when the power supply is turned off.
: When using the accumulated value hold function, calculate the product life from the operating conditions, and use the product within
its life.
Maximum updating time of the accumulated value is 1.5 million times.
If the product is operated 24 hours per day, the product life will be as follows:
•
Data memorized every 5 minutes --- 5 minutes x 1.5 million times = 7.5 million minutes = 14.3 years
•
Data memorized every 2 minutes --- 2 minutes x 1.5 million times = 3 million minutes = 5.7 years
If the accumulated flow external reset is also repeatedly used, the product life will be shorter.
<Operation>
Press the
or
button in function selection mode to display [F30].
Press the
button.
Move on to accumulated value hold setting.
Accumulated value hold setting
Press the
or
button to select the storage cycle of the
accumulated value.
Press the
button to set.
Return to function selection mode.
[F30] Accumulated value hold setting completed
: The value is stored in memory every 2 or 5 minutes. If the power supply is turned off, the accumulated flow since the last time it was
stored will be lost.
: When the power supply is turned on again, the accumulated flow count will start from the last value recorded at B.