background image

Output operation

The output operation can be selected from the following:
Output (hysteresis mode and window comparator mode) 
corresponding to instantaneous fl ow, output (accumulated output and 
pulse output) corresponding to accumulated fl ow, error output, or 
output OFF (PFMC7-L series only)

  At the time of shipment from the factory, it is set to hysteresis mode and normal output.

Delay time setting (PFMC7-L series only)

The time from when the instantaneous fl ow 
reaches the set value to when the switch 
output operates can be set. Setting the 
delay time can prevent the switch output 
from chattering.
The total switching time is the switch 
operation time and the set delay time.
(Default setting: 0 s)

0.00 s

0.05 to 0.1 s (increment of 0.01 s)

0.1 to 1.0 s (increment of 0.1 s)

1 to 10 s (increment of 1 s)

20 s
30 s
40 s
50 s
60 s

0.05 s

0.1 s

0.5 s

1 s

2 s

5 s

Display

The display of the PFMC7 series and that of the PFMC7-L series differs slightly.

For the PFMC7-L

For the PFMC7

UP button

Main screen (2-colour display)

Sub screen (

9

-digit)

Unit display

IO-Link status
indicator light

Output display
(Indicator light)

SET button

DOWN button

UP button

Main screen (2-colour display)

Sub screen (6-digit)

Unit display

Output display
(Indicator light)

SET button

DOWN button

PFMC7(-L) 

Series

Function Details

Green for ON, Red for OFF

Red for ON, Green for OFF

Red all the time

Green all the time

Display colour

The display colour can be selected for 
each output condition. The selection of 
the display colour provides visual iden-
tifi cation of abnormal values. (The display 
colour depends on OUT1 setting.)

External input function

This function can be used only when the optional external input is 
present. The accumulated fl ow, peak value, and bottom value can be 
reset remotely.

Accumulated value external reset:

A function to reset the accumulated fl ow value 
when an external input signal is applied.
In accumulated increment mode, the accumulated 
value will reset to and increase from zero.
In accumulated decrement mode, the accumulated 
value will reset to and decrease from the set value.

∗ 

  When the accumulated value is stored to memory, every time the 

accumulated value external reset is activated, the memory (EEPROM) will 
be accessed. Take into consideration that the maximum number of times 
the memory can be accessed is 1 million times. The total number of 
external inputs and the accumulated value memorizing time interval should 
not exceed 1 million times.

Peak/Bottom value reset: 

Peak and bottom value are reset.

Forced output function

The output is turned on/off in a fi xed state when starting the system 
or during maintenance. This enables the confi rmation of wiring and 
prevents system errors due to unexpected output.
For the analogue output type, when ON the output will be 5 V or 20 mA, 
and when OFF, it will be 1 V or 4 mA.

   Also, an increase or decrease of the fl ow and temperature will not 

change the on/off status of the output while the forced output function is 
activated.

Accumulated value hold

The accumulated value is not cleared even when the power supply 
is turned off.
The accumulated value is memorized every 2 or 5 minutes during 
measurement and continues from the last memorized value when 
the power supply is turned on again.
The life time of the memory device is 1 million access times. Take 
this into consideration before using this function.

Display OFF mode

This function will turn the display OFF. In this mode, decimal points 
fl ash on the main screen. If any button is pressed during this mode, 
the display reverts to normal for 30 seconds to allow checking of the 
fl ow, etc.

Setting of security code

The user can select whether a security code must be entered to 
release the key lock. At the time of shipment from the factory, it is set 
such that a security code is not required.

Peak/Bottom value display

The maximum (minimum) fl ow rate is detected and updated from 
when the power supply is turned on. In peak (bottom) value display 
mode, this maximum (minimum) fl ow rate is displayed.

Key-lock function

Prevents operation errors such as accidentally changing setting values

Standard condition: Flow rate converted to a volume at 20 °C and 1 atm (atmosphere)

Normal condition: Flow rate converted to a volume at 0 °C and 1 atm (atmosphere)

Reference condition

The display unit can be selected from standard condition or normal 
condition.

Display mode

The display mode can be selected from 
instantaneous fl ow or accumulated fl ow.

Instantaneous fl ow display

Accumulated fl ow display

Response time (Digital fi lter)

The response time can be selected to suit the application. 
(Default setting : 1 s)
Abnormalities can be detected more quickly by setting 
the response time to 0.05 seconds.
The effect of fl uctuation and fl ickering of the display can 
be reduced by setting the response time to 2 seconds.

  5 s can only be selected for the PFMC7-L series.

24

PFG300

PFMC7

PFMC7-L

Function

Details

Summary of Contents for PF2A Series

Page 1: ...product Flow ratio 2 Smallest settable increment 10 1000 1000 L type 5 500 500 L type 5 l min for t PF2A serie l PFG300 Series RoHS min the for the existing es model l Digital Flow Monitor Allows for...

Page 2: ...nding on application The accumulated indication shows the operating flow rate or residual amount of N2 etc in a gas cylinder Flow control of equipment main line and branch line Applications Remote con...

Page 3: ...sub screen is set to mode display ModE LoC is displayed when the data storage lock is enabled Except for when the version does not match or when in SIO mode Display function Displays the output commun...

Page 4: ...Visualization of settings Allows for the monitoring of remote lines Easy screen switching Simple 3 step setting Pressing the and buttons simultaneously for a minimum of 1 second will make the set valu...

Page 5: ...e output free range function Error display function Copy function Selection of power saving mode Functions pp 26 to 28 Output operation Simple setting mode Display colour Delay time setting Digital fi...

Page 6: ...flow type 1 l min PF2M7 L PFG300 PFG300 PF2A PF3A7 H L PFMB PFMC7 L 1 10 1 10 1000 1 20 2000 2 5 500 5 10 1000 1 20 2000 2 5 500 5 2 200 2 1 100 1 0 5 50 5 3 3 2 0 3 0 3 0 1 0 1 0 05 5 0 1 0 0 05 5 5...

Page 7: ...Hysteresis mode Variable Window comparator mode Variable Hysteresis mode Variable Window comparator mode Variable Hysteresis mode Variable Window comparator mode Variable Hysteresis mode Variable Win...

Page 8: ...7...

Page 9: ...L Series How to Order p 11 Specifications p 12 Flow Range p 13 Analogue Output p 13 Pressure Loss p 13 IN Side Straight Piping Length and Accuracy p 13 Internal Circuits and Wiring Examples p 14 Cons...

Page 10: ...equired order with the part numbers listed below Part no Option Note ZS 40 A Lead wire with M8 connector Length 3 m ZS 42 A Bracket Mounting screw for PFMC7501 7102 M3 x 5 2 pcs ZS 42 B Bracket Mounti...

Page 11: ...screen White Main screen 4 digits 7 segments Sub screen 6 digits 11 segments Indicator LED LED ON when switch output is ON OUT1 OUT2 Orange Environmental resistance Enclosure IP65 Withstand voltage 2...

Page 12: ...erseas use only The SI unit type is provided for use in Japan in accordance with the New Measurement Act 7 Fixed units Instantaneous flow l min Accumulated flow L Calibration certificate None A 9 Yes...

Page 13: ...2 The time from when the flow is changed by a step input when the flow rate changes from 0 to the maximum value of the rated flow range instantaneously until the analogue output reaches 90 of the rate...

Page 14: ...A current flows it is possible that the accuracy is not satisfied below 0 5 V The minimum value of the rated flow range will change according to the setting of the zero cut function 0 l min A 2 B Volt...

Page 15: ...Analogue 1 to 5 V output type PFMC7 C NPN 1 output Analogue 4 to 20 mA output type PFMC7 D Max applied voltage 28 V Max load current 80 mA Internal voltage drop 1 V or less C Analogue output 1 to 5 V...

Page 16: ...1 5 V or less L3 Analogue output 1 to 5 V or 0 to 10 V Output impedance 1 k L4 Analogue output 4 to 20 mA Max load impedance 600 Min load impedance 50 Max applied voltage 30 V Max load current 80 mA I...

Page 17: ...3 Flow rectifier Stainless steel 304 4 Sensor chip Silicon 5 Printed circuit board GE4F 6 Gasket HNBR 7 Body Aluminum alloy Anodized 8 Mesh Stainless steel 304 9 Spacer PPS 10 O ring HNBR 11 Holder St...

Page 18: ...Material Heat and oil resistant PVC Finished outside diameter 4 Symbol Model Port size A B D E F H K L N PFMC7501 7102 L Rc1 2 NPT1 2 70 30 60 6 41 2 15 14 26 18 13 6 PFMC7202 L Rc3 4 NPT3 4 G3 4 90 3...

Page 19: ...outputs NPN PNP switching type Analogue voltage output 1 2 SV 2 outputs NPN PNP switching type Analogue current output 2 XY 2 outputs NPN PNP switching type Copy function 1 Can switch between 1 to 5 V...

Page 20: ...w Unit 7 Instantaneous flow l min cfm ft3 min Accumulated flow L ft3 L x 106 ft3 x 106 Display range Instantaneous flow 25 to 525 l min 50 to 1050 l min 100 to 2100 l min Accumulated flow 9 0 to 999 9...

Page 21: ...Sensor Main circuit Main circuit Main circuit Load Load Load Load Load Load Load Load Load Load Load Load Load Load Max 28 V 80 mA Black OUT1 White OUT2 Blue DC Load Load Max 80 mA Brown DC Black OUT...

Page 22: ...llows for mounting in four orientations Bracket configuration allows for mounting in four orientations 1 6 7 2 7 2 5 2 5 2 5 2 30 30 25 1 5 2 7 7 7 20 20 Sensor connector 4 x 2 6 Depth 7 or less Power...

Page 23: ...Panel mount adapter Front protection cover Part no ZS 46 D Power supply output connection lead wire Part no ZS 46 5L Sensor connector Part no ZS 28 CA 4 1 1 to 5 V or 4 to 20 mA Pin no Terminal 1 DC...

Page 24: ...s 24 or more 31 0 0 4 24 or more 31 x n pcs 3 5 x n pcs 1 4 x R 2 o r m o r e 31 0 0 4 Dimensions Multiple 2 pcs or more secure mounting Horizontal Panel mount example Horizontal Panel mount example...

Page 25: ...external inputs and the accumulated value memorizing time interval should not exceed 1 million times Peak Bottom value reset Peak and bottom value are reset Forced output function The output is turned...

Page 26: ...ing it on again OUT2 over current error A load current of 80 mA or more is applied to the switch output OUT2 Instantaneous flow error The flow has exceeded the upper limit of the flow display range De...

Page 27: ...when OFF 1 V or 0 V when 0 to 10 V is selected or 4 mA Also an increase or decrease of the flow will not change the on off status of the output while the forced output function is activated Accumulat...

Page 28: ...pply and then turning it on again Instantaneous flow error The flow rate exceeds the maximum value of the display range Decrease the flow rate Reverse flow error There is a reverse flow equivalent to...

Page 29: ...o the slave monitors reducing setting labor and minimizing the risk of setting mistakes The set value can be copied to up to 10 flow monitors simultaneously Maximum transmission distance 4 m Selection...

Page 30: ...of SMC products with production equipment for the manufacture of weapons of mass destruction WMD or any other weapon is strictly prohibited 2 The exports of SMC products or technology from one countr...

Page 31: ...alia it Latvia 371 67817700 www smc lv info smc lv Lithuania 370 5 2308118 www smclt lt info smclt lt Netherlands 31 0 205318888 www smc nl info smc nl Norway 47 67129020 www smc norge no post smc nor...

Reviews: