background image

ITV2-TF2Z363EN 

Page 1 of 2 

 

 

Instruction Manual    

Electro-Pneumatic Regulator  

16 point Preset input type 

ITV*0*0-5****** Series 

 
 
 
 
 
 
 
 
 
The intended use of the electro-pneumatic regulator is to control the flow 
and pressure of fluid in response to preset input signals.

 

1 Safety Instructions 

These  safety  instructions  are  intended  to  prevent  hazardous  situations 
and/or  equipment  damage.  These  instructions  indicate  the  level  of 
potential hazard with the labels of “Caution,” “Warning” or “Danger.” 
They are all important notes for safety and must be followed in addition 
to International  Standards (ISO/IEC)

 *1)

, and other safety regulations. 

*1)

 ISO 4414: Pneumatic fluid power - General rules relating to systems.  

ISO 4413: Hydraulic fluid power - General rules relating to systems. 
IEC 60204-1: Safety of machinery - Electrical equipment of machines.        
(Part 1: General requirements) 
ISO  10218-1:  Robots  and  robotic  devices  -  Safety  requirements  for 
industrial robots - Part 1: Robots. 

  Refer  to  product  catalogue,  Operation  Manual  and  Handling 

Precautions for SMC Products for additional information. 

  Keep this manual in a safe place for future reference. 

 

 

Caution 

Caution indicates a hazard with a low level of risk which, if 
not avoided, could result in minor or moderate injury. 

 

Warning 

Warning indicates a hazard with a medium level of risk 
which, if not avoided, could result in death or serious injury. 

 

Danger 

Danger indicates a hazard with a high level of risk which, if 
not avoided, will result in death or serious injury. 

 Warning 

 

Always  ensure  compliance  with  relevant  safety  laws  and 
standards. 

All work must be carried out in a safe manner by a qualified person in 
compliance with applicable national regulations. 

  This  product  is  class  A  equipment  intended  for  use  in  an  industrial 

environment.  There  may  be  potential  difficulties  in  ensuring 
electromagnetic compatibility in other environments due to conducted 
or radiated disturbances. 

 Caution 

  Ensure that the air supply system is filtered to 5 microns. 

  Refer to the SMC website (URL: https//

www.smcworld.com)

 for more 

information about Safety Instructions. 

 

 

 

 

 

 

 

 

 

2 Specifications 

2.1  General specifications 

Model 

ITV*010 

ITV*030 

ITV*050 

Min. supply 
pressure 

(Set pressure) + 0.1 MPa 

Max. supply 
pressure 

0.2 MPa 

1.0 MPa 

Set pressure range  

0.005 to  

0.1 MPa 

0.005 to  

0.5 MPa 

0.005 to  

0.9 MPa 

Supply voltage 

24 VDC ± 10%, 

Current 
consumption 

0.12 A or less

 

Input signal 

16 points (no common polarity) 

Input impedance 

Approx. 4.7 kΩ 

Output signal 

NPN 

– Open collector: 30 V 80 mA 

PNP 

– Open collector: 80 mA 

Linearity 

±1% F.S. or less 

Hysteresis 

0.5% F.S. or less 

Repeatability 

±0.5% F.S. or less 

Sensitivity 

0.2% F.S. or less 

Temperature 
characteristics 

±0.12% F.S. / °C or less 

Ambient and fluid 
temperature 

0 to 50°C (no condensation) 

Pressure 
display 

Accuracy 

±3% F.S 

Min. unit 

MPa: 0.001 / kgf/cm

2

: 0.01 / bar: 0.01,  

psi: 0.1 

Note 1)

 / kPa: 1 

Enclosure rating 

Main unit: IP65, Cable connector: IP67 

Note 1)  1 PSI is the minimum display unit on the ITV*050. 

 
 
 
 

2.2  Size / Weight specifications 

Model 

ITV10*0 

ITV20*0 

ITV30*0 

Size (mm) 

50×50×109 

50×50×131 

66×66×152 

Weight (no options) 

250 g 

350 g 

645 g 

 

 Warning 

Special  products  (-X)  might  have  specifications  different  from  those 
shown in this section. Contact SMC for specific drawings. 

 

3 Installation 

3.1  Installation 

Warning 

Do not install the product unless the safety instructions have been read 
and understood. 

  This product is pre-set at the factory and must not be dismantled by 

the user. Contact your local SMC office for advice. 

  Ensure, when installing this product, that it is kept clear of power lines 

to avoid noise interference. 

  Ensure  that  load  surge  protection  is  fitted  when  inductive  loads  are 

present (i.e. solenoid, relay etc.). 

 

3.2  Environment 

Warning 

  Do not use in an environment where corrosive gases, chemicals, salt 

water or steam are present. 

  Do not use in an explosive atmosphere. 

  Do not expose to direct sunlight. Use a suitable protective cover. 

  Do  not  install  in  a  location  subject  to  vibration  or  impact.  Check  the 

product specifications. 

  Do not mount in a location exposed to radiant heat. 

 

3 Installation (continued) 

3.3  Piping 

Caution 

  Before piping make sure to clean up chips, cutting oil, dust etc. 

  When  installing  piping  or  fittings,  ensure  sealant  material  does  not 

enter inside the port. When using seal tape, leave 1 thread exposed 
on the end of the pipe/fitting.  

  Tighten fittings to the specified tightening torque. 

 

3.4  Lubrication 

Caution 

  Do not use a lubricator on the input side of this product. If lubrication 

is required, place the lubricator on the ‘output’ side so that it does not 
enter the product.  

  SMC products have been lubricated for life at manufacture, and do not 

require lubrication in service. 

  If  a  lubricant  is  to  be  used  in  the  system,  refer  to  the  catalogue  for 

details. 

 

 

 

 

 

 

 

 

 

 

 

 

4 Wiring 

 

 Caution 

Connect  the  cable  to  the  connector  on  the  main  unit  as  shown  in  the 
following diagram. Take precautions, as incorrect wiring will damage the 
unit. Use a DC power supply capable of supplying the necessary power 
requirements with minimal ripple.  

4.1  Power supply connector 

Item 

Pin assignment 

Wire colour 

Connector for 

power supply 

 

 

 

 

1. +24V 

Brown 

2. F.G. 

White 

3. GND 

Blue 

4. N.C. 

4.2  Signal connector 

Item 

Pin assignment 

Wire colour 

Connector for 

input signal 

 

1. Input 0 bit (S0) 

Brown 

2. Input 1 bit (S1) 

White 

3. Input 2 bit (S2) 

Blue 

4. Input 3 bit (S3) 

Black 

5. Input common 

Grey 

Note: Wire colours shown are when the optional cable is used. 

 

 

 
 
 
 
 

5 Settings 

 

Caution 

  Turn OFF the power supply before setting the switches. 

 

When the ‘SET’ key is operated the minimum / maximum pressure will 
be present at the outlet port. When primary pressure is applied to the 
regulator minimum pressure will be present at the outlet port. 

 

5.1  Setting Procedure 

 

Release ‘Key Lock ’as explained in section ‘Key-Lock Function’ 

 

After releasing key lock, press the ‘Set’ key again to move to F-1 

  To set the minimum pressure (display shows F-1) use up/down keys 

and 

press the ‘Set’ key to ‘Lock’ the setting. 

  To set the maximum pressure (display shows F-2) use up/down keys 

and press the ‘Set’ key to ‘Lock’ the setting.  
Note 1: If the above sequence has been followed correctly, the settings 
will complete automatically.  
Note  2:  If  only 

setting  minimum  pressure,  when  pressure  is  ‘Set’, 

pressing the set button once more will ‘skip’ to the next step. 

 

5.2  Key-Lock function 

The  keys  will  be  locked  and  cannot  be  operated  when  the  power  is 
supplied. ‘Loc’ is displayed when any keys are pushed.  
 

Key-Lock Release 

 

Press the ‘Down’ key for 2 seconds or more. 

 

Display will flash ‘Loc’ (locked). 

 

Press the ‘Set’ key to unlock. 

 

Note: To cancel press the ‘Up’ key. 

 

Key-Lock 

 

Press the ‘Up’ key for 2 seconds or more. 

 

Display will flash ‘unL’ (unlocked). 

  Press 

the ‘Set’ key to lock. 

 

Note: To cancel press the ‘Down’ key. 

 

5.3  Error Display 

If  an  abnormality  is  detected  by  the  ITV 

the LED display will show ‘Er’ 

followed by a code number. Isolate the power supply and ascertain the 
problem and solve. Re-instate the power supply after correcting any fault. 
Error codes are as shown in the table below. 
 

No 

Content 

Display 

EEProm read / write error 

Er 2 

Memory read / write error 

Er 3 

Solenoid valve fault 

Er 4 

Switch output over-current 

Er 5 

Outside of the Zero-clear range 

Er 6 

 

5.4  Reset function 

 

Press the ‘Up’ and ‘Down’ keys together for 3 seconds or more. 

  Display shows 

‘RES’. 

  Release keys to reset minimum pressure and maximum pressure. 

 

5.5  Zero-clear function 

 

Press the ‘Set’ keys together for 2 seconds or more. 

 

Press the ‘Up’ and ‘Down’ keys. Display shows ‘F03’. 

 

Press the ‘Set’ keys. Display shows ‘OcL’(Flashing). 

 

Press the ‘Up’ and ‘Down’ keys together. Display shows ‘Ocl’. 

 

Press the ‘Up’ and ‘Down’ keys together for 3 seconds or more. Display 
shows ‘clr’ (1second). 

  Zero-clear is complete. 

 

5.6  Initialization 

 

Press the ‘Set’ key together for 2 seconds or more. 

  Press th

e ‘Up’ and ‘Down’ keys. Display shows ‘F99’. 

 

Press the ‘Set’ keys. Display shows ‘ini’ (flashing). 

 

Press the ‘Up’ and ‘Down’ keys together. Display shows ‘ini’. 

 

Press the ‘Up’ and ‘Down’ keys together for 5 seconds or more. Display 
Turns OFF (1 second). 

  Initialization is complete. 

ORIGINAL INSTRUCTIONS 

 

 

 

Vs: Power 

Supply 

24 VDC 

(no polarity) 

Grey 

Reviews: