IN19856
- 16 -
Rev 2
11.
Power Connection
Power supply connector layout - PWR: M12 4-pin Plug A-coded connector
No.
Designation
Description
1
24 VDC Power (Brown Wire +24 VDC + terminal)
2
- Do Not Connect
3
0 VDC Common (Blue Wire
–
Common -terminal)
4
- Do Not Connect
Figure 6 - ITV Power Cable Pin Connections
(Note: The wire colors above are for a standard SMC power cable. Power cables from other sources
may use different colors.) For Power Cable selection, see
Accessories (Section 6)
.
12.
Networking
Network Bus In and Bus Out: M12 4-pin socket D-coded connectors
No.
Designation Description
1
TD+
Transmit Data +
2
RD+
Receive Data +
3
TD-
Transmit Data -
4
RD-
Receive Data -
Figure 7 - ITV Ethernet Cable Pin Signals
Use a standard industrial Ethernet cable. For cable selection see Accessories.
Connect one connector (“Bus In” or “Bus Out”) to the upstream device and connect the other
connector (“Bus Out” or “Bus In”) to the downstream device. For cable selection see
If Power Over Ethernet (POE) is
NOT
in use, either communications port can be used for input or
output. It is recommended that “Bus In” be used for th
e input (upstream) connection to the ITV and
“Bus Out” be used for the output (downstream) connection from the ITV. It is also recommended
that unused connectors be capped with a seal cap to meet IP65 environmental rating. For more
information see