SMC Networks ISE50 Manual Download Page 22

Selection

Warning

1. Operation

Refer to the instruction manual for the operation of the digital 
pressure switch.

2. Pressure port

Do not introduce any wire or similar object to a pressure port as 
this may damage the pressure sensor and cause a malfunction.

Mounting

Warning

1. Do not wire conjunction with power lines or 

high voltage lines.

Wire separately from power lines and high voltage lines, avoiding 
wiring in the same conduit with these lines. Control circuit 
including the switches may malfunction due to noise from these 
other lines.

2. Do not allow loads to short circuit.

Although digital pressure switches indicate excess current error if 
loads are short circuited, all incorrect wiring connections cannot be 
protected. Take precautions to avoid incorrect wiring.
As for other pressure switches, the switches will be instantly 
damaged if loads are short circuited. Take special care to avoid 
reverse wiring between the brown power supply line and the black 
output line.

3. Connect a DC (-) wire (blue) as close as 

possible to the DC power supply GND 
terminal.

Connecting the power supply away from the GND terminal can 
cause malfunctions due to noise from devices that are connected 
to the GND terminal.

4. Do not attempt to insert or pull the pressure 

sensor or its connector when the power is 
on.

Wiring

Warning

1. Monitor the internal voltage drop of the 

switch.

When operating below a specified voltage, it is possible that the 
load may be ineffective even though the pressure switch function 
is normal. Therefore, the formula below should be satisfied after 
confirming the minimum operating voltage of the load.

Caution

1. Use the switch within the specified fluid and 

ambient temperature range.

Ambient and fluid temperature operation is as follows:

Digital pressure switches: 0

 to 50

C

Take measures to prevent moisture from freezing in circuits when 
below 5

C, since this may cause damage to the O-ring and lead to 

a malfunction. The installation of an air dryer is recommended for 
eliminating condensate and moisture. Never use the switch in an 
environment where there are drastic temperature changes even 
when these temperatures are operated within the specified 
temperature range.

2. Compound pressure switch

Although application of a momentary pressure around 0.5 MPa will 
not affect the performance (at the time of vacuum break), be 
careful to not to apply constant pressure of 0.2 MPa or more.

Warning

Pressure Source

1. Do not use in an area where surges are gen-

erated.

When there are units that generate a large amount of surge in the 
area around pressure switches (e.g., solenoid type lifters, high 
frequency induction furnaces, motors), this may cause 
deterioration or damage to the switches’ internal circuitry. Avoid 
and protect against sources of surge generation and crossed 
lines.

Operating Environment

Warning

Maintenance

Caution

 

1. Da

ta of 

the digital pressure switch will be 

stored even after the power is turned off.

Input data (set pressure, etc.) will be stored in EEPROM so that 
the data will not be lost after the pressure switch is turned off. 
(Data will be stored for up to 100,000 hours after the power is 
turned off.)

—                              > 

Supply 

voltage 

Internal voltage 

drop of switch

Minimum operating

voltage of load

1. Cleaning of the switch body.

Wipe off dirt with soft cloth. If dirt does not come off easily, use a 
neutral detergent diluted with water to dampen a soft cloth. Wipe 
the switch only after squeezing the excess water out of the 
dampened cloth. Then finish off by wiping with a dry cloth 
afterwards.

19

Approved

Series

ZSE  F/ISE

Digital Pressure Switch Precautions 

Be sure to read before handling. Refer to pages 17 through 19 for safety instructions and pressure
switch precautions, and to page 20 for specific product precautions.

50

60

50

60

ZSE/ISE  4/21/02 1:15 PM  Page 22

Summary of Contents for ISE50

Page 1: ...tch Applicable for pressure detection with a wide range of fluids by using a stainless steel diaphragm F ISE ZSE High Precision Digital Pressure Switch For General Fluids 50 60 50 60 Series CAT ES100...

Page 2: ...l diaphragm Extremely low leakage To confirm absorption of work piece with water on the surface e g wet LCD glass plate To measure hydraulic pressure The stainless steel diaphragm prevents direct cont...

Page 3: ...of load lock ZSE ISE60 F A2 ZSE ISE60 F B2 1 2000 0 1kPa Positive pressure 1 1000 0 001MPa Series ZSE60F ISE60 URJ 1 4 TSJ 1 4 Model Standard thread type Special fittings for the semiconductor industr...

Page 4: ...s NPN open collector 2 output Analog output NPN open collector 2 output Auto shift input PNP open collector 2 output Analog output PNP open collector 2 output Auto shift input 22 30 62 70 Option Brack...

Page 5: ...e Ambient temperature range Ambient humidity range Withstand voltage Insulation resistance Vibration resistance Shock resistance ZSE50F Compound pressure 100 to 100kPa 100 to 100kPa 500kPa 0 1 0 001 0...

Page 6: ...OUT2 OFF ON OFF ON OFF ON OFF ON Hysteresis mode Window comparator mode Hysteresis mode Window comparator mode P_1 Large pressure and vacuum pressure Large pressure and vacuum pressure Large pressure...

Page 7: ...output 1k 12VDC to 24VDC 12VDC to 24VDC 12VDC to 24VDC 12VDC to 24VDC Main circuit Main circuit Main circuit Main circuit Load Load 6 8K 1 2K Brown DC Blue DC Black OUT 1 White OUT 2 Gray Auto shift i...

Page 8: ...d on the EEPROM When auto shift is used When the primary pressure changes set the auto shift function to Lo The pressure value at this point will be saved as the reference value to correct the pressur...

Page 9: ...sed the exce ss current turn the power supply back on Bring the pressure back to atmosp heric pressure and try using the zero out function Reduce Increase supply pressure to within the regulating pres...

Page 10: ...6 4 18 35 3 5 30 8 45 Piping port R NPT 1 4 20 20 2 M3 x 0 5 depth 4 Piping port M5 x 0 8 depth 5 30 2 6 7 1 2 4 15 2 30 2 5 10 7 7 8 Piping port G Piping port 8 45 25 1 14 5 22 10 1 12 4 G 1 4 Serie...

Page 11: ...utting dimensions for panel mounting Front protection cover 4 5 20 20 45 15 11 5 6 5 4 5 20 40 30 55 1 6 ZS 24 A Bracket A View A A 41 5 41 5 35 45 15 11 5 4 2 4 5 7 2 7 5 22 20 20 40 30 55 1 6 ZS 24...

Page 12: ...en collector 2 output Analog output PNP open collector 2 output Auto shift input 22 30 62 70 Option Bracket A Bracket D Panel mount Panel mount Front protection cover Part no ZS 24 A ZS 24 D ZS 24 E Z...

Page 13: ...to 100kPa 500kPa 0 1 0 001 0 001 0 02 1 0 1 ISE60 Positive pressure 0 000 to 1 000MPa 0 100 to 1 000MPa 1 5MPa 0 001 0 01 0 01 0 1 Possible set range 100 0 to 100 0kPa 1 000 to 1 000MPa Regulating pr...

Page 14: ...0 3 5 18 35 6 4 27 7 Piping port URJ 1 4 2 6 7 1 2 4 30 2 5 10 7 7 8 15 2 The following items are identical with those of series ZSE50F ISE50 Item Output type Example of internal circuit and wiring Au...

Page 15: ...thickness of the panel is to 3 2mm Cutting dimensions for panel mounting 41 5 1 6 55 30 40 20 20 A Bracket A ZS 24 A 4 5 20 4 5 6 5 11 5 15 45 View A 41 5 15 11 5 4 2 4 5 7 2 7 5 22 45 View A 20 20 40...

Page 16: ...sure and operates switch Normal operation Value clear Manual fine adjustment Peak hold Key lock Bottom hold Unit conversion P 14 P 16 P 14 P 15 Set Output mode Res ponse time and Auto Manual mode The...

Page 17: ...calibration SET Select the manual setting mode as the initial setting mode Press the SET button and hold it unit P_1 or n_1 appears on the display button Increases the set point value button Decrease...

Page 18: ...neously to skip to RP2 Repeat vacuum and break several times while AIL is displayed The optimum set point value is deter mined automatically Change the vacuum nozzle or other conditions of the work pi...

Page 19: ...tion returns to the measurement mode Press the SET button at least 2 seconds Release it when the display turns to UnL Press the SET button at least 4 seconds Release it when the display turns to LoC C...

Page 20: ...ally operated machinery and equipment Compressed air can be dangerous if handled incorrectly Assembly handling or repair of pneumatic systems should be performed by trained and experienced operators 3...

Page 21: ...ill cause it to break If you believe the lead wire is damaged and likely to cause malfunctions replace it 3 Confirm proper insulation of wiring Make sure that there is no faulty wiring insulation cont...

Page 22: ...measures to prevent moisture from freezing in circuits when below 5 C since this may cause damage to the O ring and lead to a malfunction The installation of an air dryer is recommended for eliminatin...

Page 23: ...torque for bracket mounting screw should be 0 98N m or less 1 Do not use in an environment with spattering liquid of oil or solvent 2 In an environment where the body of the switch is exposed to water...

Page 24: ...RALIA SMC Pneumatics Australia Pty Ltd NEW ZEALAND SMC Pneumatics N Z Ltd EUROPE AUSTRIA SMC Pneumatik GmbH CZECH SMC Industrial Automation CZ s r o DENMARK SMC Pneumatik A S FINLAND SMC Pneumatics Fi...

Reviews: