-26-
No.PS
※※
-OMJ0004-E
Troubleshooting
Applicable Pressure switch:
ISE35
If a cause applicable to the failure cannot be identified and normal operation can be recovered by
replacement with a new Pressure switch, this indicates that the Pressure switch itself was broken. The
Pressure switch breakage can be caused by operating environment (network construction, etc.), and so
consult with SMC separately to obtain countermeasures.
Yes
No
The pressure switch
does not operate
normally
Refer to reference
No. 1
The switch output is on
Go to A
The indicator light is on
The indicator light
works improperly
An error signal comes
on
The switch output is off
The switch output
generates chattering
The indicator light is off
The indicator light is off
The indicator light is on
The product is
broken
Refer to reference
No. 2
Refer to reference
No. 3
Refer to reference
No. 5
Refer to reference
No. 4
The product is
broken
The product is
broken
Refer to reference
No. 6